TP48200A-D14A1 Telecom Power
User Manual
3 Component Description
Issue 04 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
23
Table 3-3
Indicator description of rectifier
Indicator
Color
Abnormal
Status
Exception Causes
Suggestion
Run indicator Green
Off
No AC input exists
Check that the AC input voltage is
normal.
The rectifier is faulty
Replace the rectifier.
Alarm
indicator
Yellow
Steady on
Overtemperature pre-alarm
Ensure that the vent of the rectifier
is unblocked.
The rectifier hibernates
-
AC input undervoltage or
overvoltage occurs
-
Fault
indicator
Red
Steady on
Output overvoltage occurs
Remove the rectifier and then
install it again. If there is still no
output, replace the rectifier.
The fan is faulty
Replace the rectifier.
Overtemperature occurs
Ensure that the vent is unblocked
and that the ambient temperature
is within the specified range.
No output exists because of a
fault inside the rectifier
Replace the rectifier.
3.4 Power Distribution Unit
The power distribution unit distributes AC and DC power for the power system.
For details about the specifications of the power distribution unit, see Table 3-4.
Figure 3-8
Power distribution unit