6 System Commissioning
Issue Draft A (2016-05-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
73
Figure 6-8
Quick Settings screen (logging in as an advanced user)
Set the power grid code that applies to the country or region where the power station is located and
the inverter model.
Set user parameters based on the current date and time.
Set
Baud rate
,
Protocol
, and
Address
based on site requirements.
Baud rate
can be set to
4800
,
9600
, or
19200
.
Protocol
can be set to
MODBUS RTU
, and
Address
can be set to any value in the
range of 1 to 247.
When multiple inverters communicate with the SmartLogger1000 or SmartLogger2000 over RS485,
the addresses for all the inverters on each RS485 route must be within the address range set on the
SmartLogger and cannot be duplicate. Otherwise, the communication will fail. In addition, the baud
rates of all the inverters on each RS485 route must be consistent with the SmartLogger baud rate.