5. Install the terminal base on the terminal block,
and connect the shield layer to the ground point.
6. Bind the communications cable.
1. Insert the wires of the network cable to the
RJ45 connector in sequence.
RJ45 network port connection
You are recommended to use a CAT 5E
outdoor shielded network cable with an outer
diameter less than 9 mm and internal
resistance not greater than 1.5 ohms/10 m, as
well as a shielded RJ45 connector.
2. Crimp the RJ45 connector using a
crimping tool.
To ensure airtightness, you are advised to apply firestop putty to the used connectors at the bottom
of the chassis.
NOTE
No.
Color
Pin Definition
1
White-and-orange
RS485A, RS485 differential
2
Orange
RS485B, RS485 differential signal –
3
White-and-green
N/A
4
Blue
RS485A, RS485 differential
5
White-and-blue
RS485B, RS485 differential signal –
6
Green
N/A
7
White-and-brown
N/A
8
Brown
N/A
7. Use a torque wrench with an open end of 33 mm to tighten the locking caps to a torque of 7.5 N·m.
When connecting the shielded cable, choose whether to crimp the OT terminal based on site
requirements.
NOTE
11