SUN2000-(33KTL, 36KTL, 40KTL)-US
User Manual
5 Connecting Cables
Issue 07 (2019-06-20)
Copyright © Huawei Technologies Co., Ltd.
63
Figure 5-26
DC terminals
Table 5-3
DC terminal selection requirements
Number of Inputs SUN2000
1
Connects to any set.
2
Connects to sets 1 and 5.
3
Connects to sets 1, 3, and 5.
4
Connects to sets 1, 3, 5, and 7.
5
Connects to sets 1, 2, 3, 5, and 7.
6
Connects to sets 1, 2, 3, 5, 6, and 7.
7
Connects to sets 1, 2, 3, 4, 5, 6, and 7.
8
Connects to sets 1, 2, 3, 4, 5, 6, 7, and 8.
DC input power cable specifications
lists the recommended DC input power cable specifications.
Table 5-4
Recommended DC input power cable specifications
Cable Type
Conductor Cross-Sectional Area
Cable Outer
Diameter
Range
Recommended
Value
Common PV cables in
the industry (model:
PV1-F)
12–10 AWG
12 AWG
4.5–7.8 mm
(0.18–0.31 in.)
Rigid cables, such as armored cables, are not recommended, because poor contact may be
caused by the bending of the cables.