3.2.2 Setting SNMP Parameters
Prerequisites
NO TE
You can set SNMP parameters remotely or locally on the WebUI.
Before setting SNMP parameters, obtain the information listed in
from
the SNMP NMS.
Table 3-3 Information obtained from the NMS
Item
Description
SNMP Version
SNMP version and port number used
for communication between the SMU
and NMS. The SNMP version can be
SNMPv1, SNMPv2c, or SNMPv3.
SNMP Port
Read Community Name
If you use SNMPv1 or SNMPv2c, enter
the read and write community names
that comply with the NMS. Otherwise,
the SMU will not connect to the NMS.
The read community name must be
different from the write community
name.
Write Community Name
User Name
To enhance the security, you need a
user name and password for
authentication if you use SNMPv3.
After the authentication succeeds, the
SMU can communicate with the NMS.
MD5/SHA Password
DES/AES Password
Trap Target Address
IP address and port number used for
reporting alarm trap packets.
Trap Port
Trap Community
If you use SNMPv1 or SNMPv2c,
community name used for reporting
alarm trap packets.
Procedure
Step 1 Log in to the WebUI.
NO TE
The initial user name is admin, and the initial password is Changeme.
Step 2 Access the System Settings page and set SNMP.
SMU11B Site Monitoring Unit
User Manual
3 NMS Management
Issue 03 (2022-06-06)
Copyright © Huawei Technologies Co., Ltd.
15