Error Code
Troubleshooting Suggestion
Error Code
Troubleshooting Suggestion
0x200b
1.
Check whether the DNS server
address is correct.
2.
Check whether the domain
name or IP address of the
SMTP server are correct.
3.
Check whether the network
communication between the
SmartLogger and DNS is
normal.
0x4016
1.
Try again later.
2.
Check whether the DNS server
address is correct.
3.
Check whether the domain name
or IP address of the SMTP
server are correct.
0x406e
Confirm the encryption mode and
port supported by the mailbox, and
check whether they are correctly
configured.
0x8217
1.
Check whether the user name
and password are correct.
2.
Log in to the mailbox of the
email sender and start the SMTP
service.
3.
Log in to the mailbox of the
email sender and start the
third-party client license code
function.
0xa003
Check whether the domain name
or IP address of the SMTP server
are correct.
0xa005
Check whether the user name is
correct.
0xa006
Check whether the user password
is correct.
0xe002
No domain name or IP address is
configured for the SMTP server.
Configure the domain name and IP
correctly.
0xe003
Configure the addresses for
sending and receiving emails
correctly.
Other error
codes
Provide SmartLogger run logs and
contact Huawei technical support.
7.10.4 Port Settings
7.10.4.1 Setting DO Parameters
The SmartLogger provides three DO ports, which support external router reset and the audible
and visual alarm for grounding faults.
Connecting a 3G Router over the DO Port
Considering the restrictions on the current that can pass through the DO port of the
SmartLogger, you need to determine the number of DO ports to be used for the control based
on the maximum power supply current of the 3G router (the maximum power supply current
can be calculated based on the maximum power consumption and DC power supply voltage).
When the power supply current is smaller than 1 A, use one DO port.
When the power supply current is larger than 1 A but smaller than 1.6 A, use two DO
ports.