100
Alarm
ID
Alarm Name
Severity
Cause
Solution
EPO
activated.
0624
Not ready
Critical
The ready switch is off.
Turn the ready switch to the
locked position.
0625
Inter-battery
cabinet parallel
cable alarm
Minor
The communications cable
between cabinets is not
properly connected.
Check the cable connection of
the inter-rack parallel cable.
0628
Abnormal signal
board
Critical
The signal transfer board is
faulty.
Check the cable connection
to the signal transfer board.
Replace the signal transfer
board.
0629
Abnormal
inter-battery
cabinet parallel
cable
Critical
The inter-rack parallel
cable is not properly
connected.
The inter-rack parallel
system CAN is faulty.
The 1# battery
management module is
faulty or the connected 2#
battery management
module is faulty.
Check whether the
inter-rack parallel cable is
loose.
Replace the inter-rack
parallel cable.
Replace the battery
management module or the
signal transfer board.
0630
Abnormal
intra-battery
cabinet parallel
cable
Critical
The intra-rack parallel
CAN is faulty.
The RS485
communications cable in
the rack is faulty.
he battery management
module is not properly
connected to the signal
transfer board.
Check whether the cable to
the signal transfer board is
loose.
Check whether the signal
terminal between the battery
modules is properly
connected.
Replace the parallel cable
between the battery module
and the signal transfer
board.
Replace the battery
management module or the
signal transfer board.
0631
Version
incompatible
Critical
The battery module
software is incompatible.
The software version does
not match the battery
management module.
The DSP software version
does not match the battery
management module.
The FPGA software
version does not match the
battery management
Load the software.