Sealing putty
Paper
protective film
12
5
Verifying the Installation
1. Check that there is no foreign matter at the top
and bottom of the cabinets, copper bars,
switches, and the rear of units.
2. Check that the battery cables are correctly
connected.
3. After verifying the installation, reinstall all the
covers.
4. (Remove the paper protective film from the
sealing putty.) After routing cables and verifying
cable connections, seal the gap between cables
and the cabinet using sealing putty.
5. Do not remove the dustproof cover before
power-on to prevent dust inside the SmartLi.
Sealing putty must be used
as a whole and the gap can
be sealed only from the top.
Top dustproof cover
Rear dustproof cover
Front dustproof cover
6
Powering On
1. On the UPS LCD screen, set
System Info > Settings > Battery Settings > Battery Type
to
Lithium battery
.
• The
BCB off
alarm is displayed on the UPS LCD and SmartLi LCD (the red indicator is steady
on). No action is required. After the battery circuit breaker is closed, the alarm is automatically
cleared.
• After the battery monitor unit is started, the green indicator is on for 1s and then off for 4s.
• If multiple SmartLi cabinets are combined, press and hold the POWER ON/OFF button on the
battery monitor unit of the master cabinet for more than 2 seconds to power on the master
cabinet. Then, power on slave cabinets one by one in the same way.
• Upgrade the UPS software to the version that supports lithium battery connection. See
UPS5000 The Relationship of Software Version
to check the version number.
•
Thres. of low batt. volt. over dry contact (V/cell)
: If you set
Batt. Volt. Below Threshold
for
an output dry contact and the battery voltage is lower than this threshold, the output dry
contact will output signals accordingly. (Set on the UPS)
• Turn on the ready switch on the battery monitor unit.
• When the UPS is in normal mode, ensure that the UPS is running stably before turning on the
battery circuit breaker on the SmartLi.
2. Press and hold the POWER ON/OFF button on the battery monitor unit for more than 2s. The
green indicator of the battery monitor unit blinks at 4 Hz.