21
Category
Status (Blinking slowly: On for 1s and then Off for 1s;
Blinking fast: On for 0.2s and then Off for 0.2s)
Description
Run
indication
LED1
LED2
N/A
Steady green
Steady green
The solar inverter operates in
the grid-tied mode.
Blinking green at long
intervals
Off
The DC is on and the AC is
off.
Blinking green at long
intervals
Blinking green at long intervals
Both DC and AC are on, and
the solar inverter is not
connected to the power grid.
Off
Off
The DC is off, and the AC
may be energized (Ensure
that the external AC switch is
OFF).
Steady red
Steady red
Fault
Communic
ation
indication
LED3
N/A
Blinking green at short intervals
The solar inverter is in
communication.
Off
No communication
Preparations and WebUI Login
1
System Commissioning (SmartLogger1000A WebUI)
1. Connect the network cable between the network port on the PC and the ETH port on the
SmartLogger1000A.
2. Set the IP addresses of the PC and SmartLogger1000A in the same network segment.
Item
SmartLogger Default Value
Example PC Setting
IP address
192.168.0.10
192.168.0.11
Subnet mask
255.255.255.0
255.255.255.0
Default gateway
192.168.0.1
192.168.0.1
1. Use the SmartLogger1000A to set parameters for the SUN2000-4.95KTL-JPL0.
2. Operating system: Windows 7 or later versions
3. Browser: Chrome 52, Firefox 58, Internet Explorer 9, or their later versions
4. The WebUI snapshots are for reference only, and the actual display prevails.
Summary of Contents for SmartACBox