4

2. Install emergency shutdown cables.

Connecting Output Power Cables

3.3

Connecting Output Power Cables (Used with an Address Board)

3. Install CAN communications cables.

1. Install DC output power cables.

• The metal terminals are delivered together with the DC output terminal.
• The recommended crimping tool is XCXY-02. The locator model is DWQ-18.
• Recommended heat-shrink tubing diameter: 6 mm; recommended temperature resistance: 125

°

C; recommended baking temperature: 

110

°

C

• The metal terminals must be reliably crimped. Minimum pulling-out force: 300 N for the cross-sectional area 5.26 mm

2

or 350 N for the 

cross-sectional area 6 mm

2

.

NOTE

The DC output terminal can be installed in the following two scenarios. Install it based on the site requirement.
• Used with an address board (DC output terminal and address board supplied by the user)
• Not used with an address board (DC output terminal supplied by the user)

A 120-ohm resistor must be connected in parallel between the cables of the first and last chargers. Otherwise, communication may be poor.

Keep a distance of 3

–5 mm between the front end of the heat shrink tubing and the metal terminal buckle.

Summary of Contents for R95021G1

Page 1: ...ing ear optional 8 DC output port 9 AC input port Model R95021G1 Weight 12 kg without packaging 14 kg with packaging Dimensions H x W x D 83 mm x 206 mm x 470 mm Front Rear Copyright Huawei Technologies Co Ltd 2018 All rights reserved 1 The information in this document is subject to change due to version upgrades or other reasons Every effort has been made in the preparation of this document to en...

Page 2: ...idewards or vertically with the panel at the bottom If side or vertical installation is adopted ensure that mechanical parts are designed to avoid interference The installation mode can be selected according to the actual situation Horizontal installation is recommended and vertical installation is not recommended Horizontal Installation Recommended 1 Optional Determine whether to install the moun...

Page 3: ...ture resisting cables Cross sectional area 6 mm2 BVR ZR 105 flame retardant 105 C flexible wire CAN communications cable Shielded twisted pair minimum cross sectional area 0 08 mm2 28 AWG maximum cross sectional area 1 5 mm2 16 AWG N A Preparing Cables 3 1 DC output DC output address line charger in position detection and control ground signals are hazardous voltages please don t touch Input Termi...

Page 4: ... metal terminals must be reliably crimped Minimum pulling out force 300 N for the cross sectional area 5 26 mm2 or 350 N for the cross sectional area 6 mm2 NOTE The DC output terminal can be installed in the following two scenarios Install it based on the site requirement Used with an address board DC output terminal and address board supplied by the user Not used with an address board DC output t...

Page 5: ...sectional area 5 26 mm2 or 350 N for the cross sectional area 6 mm2 NOTE Huawei Technologies Co Ltd Huawei Industrial Base Bantian Longgang Shenzhen 518129 People s Republic of China www huawei com Email solarservice huawei com 4 Set the address DIP switch Hardware address 6 x ON switch No of S1 1 ON switch No of S2 Switches 1 6 of S1 correspond to row addresses 1 6 Switches 1 6 of S2 correspond t...

Reviews: