Huawei R50040G1 Quick Manual Download Page 4

4

Connecting Output Power Cables (Not Used with an Address Board)

Connecting AC Input Power Cables

3.4

Power-On Check

3.5

After installation and power-on, use a multimeter to check whether the voltage at the cabinet copper bar connected to the output terminal of the charger is within 
the normal range (200

–500 V DC). Check that the green indicator on the charger is steady on, indicating that the charger is running properly.

4

Maintenance

To ensure that the charger can operate properly for a long term, you are advised to perform routine maintenance on it as described in this chapter.

The product has the maintenance-free class B and the MTTR of at most 1 h. The charger is hot swappable and should be replaced if it is faulty.

The air filter of the cabinet needs to be cleaned regularly to avoid dust buildup at the air inlet as dust can cause overheating inside the charger.

Indicator

Status

Description

Solution

Alarm 
indicator 
(yellow)

Steady 
on

Ambient overtemperature alarm

AC input overvoltage, 
undervoltage, open phase, or 
serious voltage imbalance

Slight current imbalance

Soft address abnormality alarm

Ambient undertemperature
alarm 

Protection caused by other 
abnormalities

Check that the input power 
cables and power 
distribution circuit breakers 
of the charging machine 
(pile) or station cabinet are 
normal.
If the alarm persists, 
contact Huawei customer 
service center.

Blinking

The charger has failed to 
communicate. 

Check that the CAN 
communications cable is 
correctly connected and the 
build-out resistor is installed 
as required.
If the alarm persists, 
contact Huawei customer 
service center.

Fault 
indicator (red)

Steady 
on

Lockout due to output 
overvoltage

Serious current imbalance

Fan fault

Communication failure between 
the primary side and the 
secondary side

Unrecoverable no-output 
breakdown

Poor connection

Lockout due to an output short 
circuit

Abnormal detection of the 
hardware address board

Abnormal output discharge 
circuit

Faults caused by other 
abnormalities

Contact Huawei customer 
service center.

5

Troubleshooting

Scan here for more 
documents:

Support

Scan here for Huawei 
technical support:

iOS

Android

You can also log in to Huawei technical support 
website: http://support.huawei.com

The metal terminals are delivered together with the AC input terminal.

The recommended crimping tool is XCXY-02. The locator model is DWQ-18.

Recommended heat-shrink tubing diameter: 6 mm; recommended temperature resistance: 125

°

C; recommended baking temperature:  110

°

C

The metal terminals must be reliably crimped. Minimum pulling-out force: 300 N for the cross-sectional area 10 AWG or 350 N for the cross-sectional area 6 mm

2

.

NOTE

To install the technical support app, scan the iOS or Android 
QR code. To access the technical support website, scan the 
Support QR code. After logging in to the technical support app 
or website, you can search for the device model to view or 
obtain more information.

NOTE

Huawei Technologies Co., Ltd.

Huawei Industrial Base, Bantian, Longgang

Shenzhen 518129 People's Republic of China

www.huawei.com

Email: [email protected]

Summary of Contents for R50040G1

Page 1: ...llution sources such as chemical factories rubber plants and electroplating factories Areas within 1 km away from light pollution sources such as food factories tanneries and heating boilers Installation Environment and Hole Size Requirements 2 1 Installing the Charger 2 2 Application scope charging machine pile or station The charger can be installed horizontally sidewards or vertically with the ...

Page 2: ...ss sectional area 0 08 mm2 maximum cross sectional area 1 5 mm2 wire minimum cross sectional area 28 AWG wire maximum cross sectional area 16 AWG Preparing Cables 3 1 Side Installation Vertical Installation Not Recommended Horizontal Installation Recommended 1 Optional Determine whether to install the mounting ear based on the site requirement 2 Slowly push the charger into the slot 3 Tighten the ...

Page 3: ... The address extension function is disabled Two address setting switches are used on the address board to set the address Up to 36 addresses can be set Hardware address Row address 1 x 6 Column address The address extension function is enabled One extension switch and two address setting switches are used on the address board to set the address Up to 64 addresses can be set Hardware address Extend...

Page 4: ...that the CAN communications cable is correctly connected and the build out resistor is installed as required If the alarm persists contact Huawei customer service center Fault indicator red Steady on Lockout due to output overvoltage Serious current imbalance Fan fault Communication failure between the primary side and the secondary side Unrecoverable no output breakdown Poor connection Lockout du...

Reviews: