Huawei R50040G1 Quick Manual Download Page 2

2

Preparing Terminals

3.2

Port

Name

Function

Remarks

P1

NC

None

-

P2, P3

DC+

DC 

DC output of the 
charger

P4, P5

DC-

DC output 

A1

ADDRESS_0

Address line (row address)

Connects to the 
address board.

B1

ADDRESS_1

Address line (column 
address)

C1

ADDRESS_IO

Address extension 
(extended address)

A2

NC

None

-

B2

LINK_CHECK

Charger in-position 
detection

B2 and C2 need to be 
short-circuited.

C2

SEC_GND

Control ground

A3, B3, C3, A4, B4, 
C4, A5

NC

None

-

B5

CANBL

CAN signal line

Cascades to the 
monitoring module of 
the system.

C5

CANBH

CAN signal line

Output Terminal Appearance

Output Terminal Port 

Definitions

Used with an address board, Huawei-supplied

Not used with an address board, user-supplied; 
recommended model: AVIC Jonhon CZ36E-20Z 

3

Electrical Connection

Determine the heat resistance grade of the cable insulation material based on the ambient temperature.  It is recommended that the cables resist heat of at 
least 105

°

C.

Port

Recommended Cable Specifications  (Choose Any of the Following)

Remarks

DC output power 
cable

Cross-sectional area 6 mm

2

(H07Z-K, UL3386, or equivalent cables able to work for a long term 

at 105

°

C)

Two cables are required. If the cable 
surface temperature  is higher than 90

°

C, 

use high temperature-resisting cables.

Cross-sectional area 10 AWG (UL1015 material 105

°

C)

Cross-sectional area 6 mm

2

(BVR-ZR-105, flame retardant,  105

°

C, flexible wire)

AC input power cable

Cross-sectional area 6 mm

2

(H07Z-K, UL3386, or equivalent cables able to work for a long term 

at 105

°

C)

If the cable surface temperature  is higher 
than 90

°

C, use high temperature-resisting 

cables.

Cross-sectional area 10 AWG (UL1015 material 105

°

C)

Cross-sectional area 6 mm

2

(BVR-ZR-105, flame retardant,  105

°

C, flexible wire)

CAN communications 
cable

Shielded twisted pair: minimum cross-sectional area 0.08 mm

2

, maximum cross-sectional area 

1.5 mm

2

; wire minimum cross-sectional area 28 AWG, wire maximum cross-sectional area 16 

AWG

-

Preparing Cables

3.1

Side Installation

Vertical Installation (Not Recommended

)

Horizontal Installation 

(Recommended)

1. (Optional) Determine whether to install the 

mounting ear based on the site 
requirement.

2. Slowly push the charger into the slot.
3. Tighten the screws in the middle of the 

panel. Then, install and tighten the screws 
in the lower and upper parts of the panel 
as well as the screws on the mounting ear.

4. After the installation is complete, seal the 

cable holes of the cabinet.

Vertical 
installation is not 
recommended 
because doing 
so will cause 
maintenance 
difficulty as you 
will be unable to 
locally check 
whether the 
charger is 
running (the 
indicators are 
invisible 
because the 
panel faces 
downwards).

NOTICE

NOTICE

The user needs to supply 
a terminal for connecting 
to this port. You are 
advised to use the 
Weidmüller terminal model 
BCZ 3.81/02/180 SN GN 
BX.

Pins B2 and C2 of the DC output terminal must be short-circuited.  Otherwise, the 
charger cannot be started. The terminal to be used with an address board is 
supplied by Huawei, and the pins are short-circuited before delivery. The output 
terminal not used with an address board needs to be supplied by the user, and the 
user needs to short-circuit the pins. 

NOTICE

DC , DC output 

–, address line, charger in-position 

detection, and control ground signals are hazardous voltages 
so basic insulation is designed between these signals and the 
enclosure.

The CAN signal line is a safety extra-low  voltage (SELV). 
Functional insulation is designed between this signal and the 
enclosure; enhanced insulation is designed between this 
signal and hazardous voltages.

This document uses a Huawei-supplied address board as an 
example. For details about how to use a user-supplied 
address board, see the 

Charger Terminal and Address Board 

Quick Guide

.

NOTICE

Summary of Contents for R50040G1

Page 1: ...llution sources such as chemical factories rubber plants and electroplating factories Areas within 1 km away from light pollution sources such as food factories tanneries and heating boilers Installation Environment and Hole Size Requirements 2 1 Installing the Charger 2 2 Application scope charging machine pile or station The charger can be installed horizontally sidewards or vertically with the ...

Page 2: ...ss sectional area 0 08 mm2 maximum cross sectional area 1 5 mm2 wire minimum cross sectional area 28 AWG wire maximum cross sectional area 16 AWG Preparing Cables 3 1 Side Installation Vertical Installation Not Recommended Horizontal Installation Recommended 1 Optional Determine whether to install the mounting ear based on the site requirement 2 Slowly push the charger into the slot 3 Tighten the ...

Page 3: ... The address extension function is disabled Two address setting switches are used on the address board to set the address Up to 36 addresses can be set Hardware address Row address 1 x 6 Column address The address extension function is enabled One extension switch and two address setting switches are used on the address board to set the address Up to 64 addresses can be set Hardware address Extend...

Page 4: ...that the CAN communications cable is correctly connected and the build out resistor is installed as required If the alarm persists contact Huawei customer service center Fault indicator red Steady on Lockout due to output overvoltage Serious current imbalance Fan fault Communication failure between the primary side and the secondary side Unrecoverable no output breakdown Poor connection Lockout du...

Reviews: