Appendix: Tie Wrapping and Labeling
The spacing between power cables, ground cables, and signaling cables must be larger than 30 mm.
Inside the cabinet, the cables must be tied neatly to form a rectangle cross section, and the cable ties must face the same direction.
Each bundle cannot have more than 20 cables. The cables must be tied every 200 mm and the cables must be fixed to the cabinet.
The cables must be labeled 20 mm away from both ends.
Label location
Ports
20mm
1 - A01 - 2 - A - 09
TO:
1 - A01 - 2 - A - 08
TO:
1 - A01 - 2 - A - 07
TO:
1 - A01 - 2 - A - 06
TO:
Cable
Fold to the right
Fold upward
Labeling process
Sticky side
Cable
Cable
1 - A01 - 2 - A - 06
TO:
Do not tie cables at bends.
Do not cut ties in a way
that creates pointed ends.
Cables must be neatly tied.
Cable manager
Cross section of the cable bundle
200mm
200mm
Cross section of the cable bundle
Cable manager
Tie Wrapping Requirements
1
2
3