Figure 3-28 Securing the NetCol5000-C to the base
----End
3.8 Connecting Water Pipes
3.8.1 Connect Automatic Drainpipe
Context
NO TICE
● The external drainpipe must have a certain gradient (> 1:50), and no
accumulated water is allowed.
● The entire drainpipe should be closely wrapped with thermal insulation foam.
● The drainpipe can be secured along the door post using cable ties inside a
cabinet.
Procedure
Step 1 Remove the drainpipe plug.
Step 2 Install a pipe adapter and seal it with sealant.
Step 3 Connect the PPR water pipe using a heat gun and wrap the pipe with thermal
insulation foam.
NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
3 Installation
Issue 03 (2020-08-30)