NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
6 System Operation and Maintenance
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
150
Component
Item
(On the Basis of Monthly
Maintenance)
Troubleshooting
Water detector
Check that the water detector is
securely installed.
N/A
6.3 Alarm reference
describes alarms for the in-row air cooled smart cooling product NetCol5000-A.
Table 6-5
Alarm reference
Alarm
ID
Alarm Name
Alarm
Severity
Impact
Possible Causes
Solution
a001
Return-air 1
temp invalid
Major
The alarm is
generated.
1.
The cables to
the temp sensor
are loose or
damaged.
2.
The temp
sensor is faulty.
1.
Check the cables to the
temp sensor.
2.
Maintain or replace the
temp sensor.
Return-air 2
temp invalid
Major
The alarm is
generated.
1.
Dirt or water
exists around
the T/H sensor,
which leads to a
detection fault.
2.
The temp
sensor is faulty.
1.
Remove dirt or water from
the T/H sensor.
2.
Maintain or replace the
temp sensor.
a002
Return-air HT
Critical
The alarm is
generated.
1.
The load is high
or the
refrigeration
capacity is
insufficient.
2.
The return air
temp is higher
than the
return-air HT
alarm threshold
during startup.
3.
The ambient
temp is high.
4.
The return-air
HT alarm
threshold is
inappropriate.
5.
The temp
displayed is
different from
1.
Add more smart cooling
product units.
2.
Check other causes if the
alarm persists after startup.
3.
Check the ambient temp.
4.
Adjust the return-air HT
alarm threshold.
5.
Calibrate or replace the
abnormal sensors.