5 Power-On Commissioning
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
142
Step 7
(Optional) Commission the humidifier.
1.
On the home screen, Choose
Maint
>
Diagnostic Mode
>
Enter
and set
Humidifier
to
50%
.
2.
The water supply valve opens and water is charged into the humidifier cylinder
automatically. After the water level reaches a threshold, the water supply valve closes.
You need to check that the water inlet pipe does not leak during the process.
3.
After 3 to 10 minutes, choose
Running
>
Device Details
>
Humidifier
and check that
the value of
Current in cylinder
is greater than 1.2 A and that no alarm is generated,
which means that the humidifier works properly.
4.
On the home screen, Choose
Maint
>
Diagnostic Mode
>
Enter
, set
Humidifier
to
0%
,
and then click On after
Water inlet solenoid valve
. The humidifier cylinder starts to
drain water. You need to check that the drainpipe does not leak during the process.
Step 8
(Optional) Commission the water pump. Open the cover in front of the water pan and lift the
low liquid level detector. The pump starts working after 5 seconds. Then release the liquid
level detector and shut down the pump.
It is normal if a pump alarm is generated during the pump operation when there is no water in the pan.
The pump generates this alarm for self-protection.
Step 9
After the commissioning is complete, remove the device used for charging the refrigerant, and
install the valve bonnet.
Step 10
On the
Diagnostic Mode
screen, tap
Exit
and then
Yes
to exit the diagnostic mode.
Step 11
Check the teamwork control cables and set the teamwork control parameters. For details
about how to commission, see
4.3.2.5 Setting Teamwork Control Parameters
Step 12
Go back to the startup screen, and tap
Shutdown
.
----End
Follow-up Procedure
After the commissioning or maintenance is complete, clean the oil stains on the copper pipe
thermal insulation foam or bottom plate if there is any.
5.6 Powering Off the Equipment
Procedure
Step 1
Tap
Shutdown
on the home screen of the LCD.