4 ACC Introduction
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
96
4.3.2.4 Setting Communications Parameters (Modbus Settings)
Procedure
Step 1
Choose
Settings
>
Comm Settings
>
Modbus Settings
on the home page. The page shown
Figure 4-8
Setting Modbus communications parameters
Step 2
Set the parameters by following instructions in
Table 4-4
Modbus parameter settings
Parameter
Specification Setting Method
Protocol
Modbus RTU
Modbus RTU: If a smart cooling product needs to
connect to an EMS using an RS485 cable, set
Protocol
to
Modbus RTU
.
Baud rate
9600, 19200
Set the baud rate as required. The value should be
consistent with that at the EMS side. This parameter is
configurable when
Protocol
is set to
Modbus RTU
.
Comm
address
1–255
Set the address of the smart cooling product. The EMS
communicates with the smart cooling product through
this address, and the addresses of two smart cooling
products connected to the same EMS must be unique.
This parameter is configurable when
Protocol
is set to
Modbus RTU
.
----End