NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
5 Operation and Maintenance
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
133
5.2 Alarm Reference
describes the alarm reference of the NetCol5000-A.
If the
Clear
icon is displayed on the
Details screen
, the alarm can be manually cleared by
tapping the
Clear
button after the fault is rectified. The alarm clearance type (automatic or
manual) varies with precision air conditioners. Alarms can be cleared are a009, a013, a025,
a046, a058, a061, a062, a064, a079, a095, a130, a137, a179, a182, a190.
Table 5-5
Alarm description
Alarm
ID
Alarm
Alarm
Severity
Impact
Possible Cause
Solution
a001
Return-air
1 temp
invalid
Return-air
2 temp
invalid
Major
The alarm
is
generated.
1.
The cables to the T/H
sensor are loose or
damaged
2.
The T/H sensor is faulty.
1.
Remove dirt or water
from the T/H sensor.
2.
Maintain or replace the
T/H sensor.
a002
Return-air
HT
Critical
The alarm
is
generated.
1.
The load is high or the
refrigeration capacity is
insufficient.
2.
The ambient temp is
high.
3.
The return-air HT alarm
threshold is
inappropriate.
4.
The temp displayed is
different from the actual
temp.
1.
Add more air conditioner
units or Consult
Huawei technical
support.
2.
Check other causes if the
alarm persists after
startup.
3.
Adjust the return-air HT
alarm threshold.
4.
Calibrate or replace the
abnormal sensors.
a003
Return air
LT
Warning
The alarm
is
generated.
1.
The load is low.
2.
The ambient temp is low.
3.
The return-air LT alarm
threshold is
inappropriate.
4.
The temp displayed is
different from the actual
temp.
1.
Please consult Huawei
technical support.
2.
Check other causes if the
alarm persists after
startup.
3.
Adjust the
undertemperature alarm
threshold.
4.
Calibrate or replace the
abnormal sensors.
a004
Return-air
2 humid
invalid
Major
The alarm
is
generated.
1.
The cables to the T/H
sensor are loose or
damaged.
2.
The T/H sensor is faulty.
1.
Remove dirt or water
from the T/H sensor.
2.
Maintain or replace the
T/H sensor.
a007
Return-air
Major
The alarm
1.
The cables to the T/H
1.
Check the cables to the