32
Connect the ground cable of the cabinet
to the ground bar of the equipment room.
Specifications: 25030190
electrical power cable - 450
V/750 V - 60227 IEC 02 (RV) -
10 mm^2 - yellow/green - 62 A
Color: yellow-green
Obtaining method: auxiliary
material package
5
(Optional) Combine the cabinets.
6
Ground the cabinet.
Ground cable
of the cabinet
If two or more cabinets are required, these cabinets must be combined. Ignore this
operation if only one cabinet is required.
Unscrew the connecting plates on the front door
and rear doors using a Phillips screwdriver.
Pass the connecting plate through the gap on the
cabinet door and secure it using the screws
removed during step 1.
The figure on the right shows that the cabinets are
combined using connecting plates.
There are four connecting points on the front door
and rear door of the middle cabinets.
There are two connecting points on the front door
and rear door of the side cabinets.
Ensure that the vertical deviation and the
distance between cabinets are not greater than 3
mm after the cabinets are combined.
Route the cabinet ground cable from position A
to the upper cable outlet or from position B to
the bottom cable outlet.
This operation must be performed by professional
electricians onsite.