UPS+ UPSN UPS-
BAT N
BAT-
BAT+
40 batteries
01
02
03
04
05
10
09
08
07
06
11
12
13
14
15
20
19
18
17
16
21
22
23
24
25
30
29
28
27
26
35
34
33
32
39
38
37
36
31
40
1. Serial number label paste instructions: Label paste on battery surface,
sorting,
Notes:
1QF Battery Cabinet-2
Battery Cabinet-1
Material
Name
Code
Specifications
Purpose
Quantit
y
Battery
24022490
Battery, VRLA battery, 12V, 100Ah, 12V
monomer, 330mm (width) * 174mm (depth) *
222mm (height), 1, Shuangdeng 6-GFM-100,
UPS dedicated battery
UPS dedicated battery
40pcs
Terminal
14170552
Bare crimp terminal -JG-95mm^2-M6-250A-tin
Wiring terminals between batterie
90pcs
Cable
25033516
Electronic power cable
-600V/1000V-WDZB-YJY-95mm^2- black, low
smoke zero halogen, CE
Connecting Cables Between Batteries
74m
Terminal
1417016
4
Bare crimp terminal -JG-95mm^2-M12-320A-tin
Battery switch wiring termina
6pcs
NO.P009 Battery Wiring Diagram
Summary of Contents for FusionModule1000A40 ICT Solution
Page 11: ...NO S003 Pre fab Module Grounding Position Diagram ...
Page 12: ...NO S005 External Cable Tray Installation Position Diagram ...
Page 13: ...NO S006 Fire Hammer Installation Position Diagram ...
Page 14: ...NO S007 FIG rain eave mounting position ...
Page 15: ...Pipe window NO S004 Pre fab Module Pipe Installation Position Diagram ...