background image

12

CAN te RS485 monitoring

2. Connect teamwork and monitoring communications cables.

Networking

Teamwork

Monitoring

Protocol

CAN

Modbus-RTU

Connect the COM/FE port on the main control module of the last smart cooling product in each 

group to the RS485 port on the host.

CAN te FE monitoring

Networking

Teamwork

Monitoring

Protocol

CAN

Modbus-TCP/SNMP

Customers can purchase Huawei's switch and NetEco for the monitoring system.

Summary of Contents for FusionCol8000-C210

Page 1: ...HUAWEI TECHNOLOGIES CO LTD FusionCol8000 C210 In room Chilled Water Smart Cooling Product Quick Guide Issue 04 Part Number 31500ECR Date 2022 06 30 ...

Page 2: ...on foam dedicated glue for thermal insulation foam and thread sealant 2 Engineering Materials Product Model Pipe Routing Cable Routing Dimensions Without Packing H x W x D mm FusionCol8000 C210 Routed from top Routed from top 2450 x 2350 x 1100 3 Installing the Equipment 1 Read the related user manual or instructions before installing the FusionCol8000 C 2 The unit in this document is a fully conf...

Page 3: ...e is a hiss sound the system is well sealed and you need to open the exhaust valve to exhaust the nitrogen If there is no hiss sound contact Huawei technical support You can open or close the exhaust valve using a flat head screwdriver Slowly open the exhaust valve to release nitrogen After the nitrogen is exhausted close the exhaust valve Removing Air Filters 3 1 ...

Page 4: ...M12 expansion bolts 2 Install anchor baffle plates at the bottom Secured with Supports Obtain the connecting kits and screws according to the packing list A distance of at least 15 mm must be reserved between combined cabinets Securing the Equipment 3 4 Display side Display side 1 Secure the equipment to the base using four M12x45 bolt assemblies 2 Install anchor baffle plates at the bottom Dimens...

Page 5: ...se M6x25 screws to secure the both sides of the air duct to the both sides of the equipment Pipe support 1 A 1 100 tilt should be reserved for the drainpipe and humidifier water inlet pipe 2 Keep a clearance of at least 25 mm between pipes Secure the pipes to supports every a certain distance 3 Clean the water inlet engineering pipes to avoid impurities entering into the humidifier 4 A reducing va...

Page 6: ... the reserved pipe clamp on the cabinet side to the top of the cabinet and route the hose through the humidifier water inlet hose hole 3 Connect the water inlet hose of the smart cooling product to the engineering pipe Connecting the Chilled Water Inlet and Outlet Pipes 4 4 1 Wrap thermal insulation foam around the whole pipes after pipes are connected 2 Due to the hardening property of yellow adh...

Page 7: ...th Nitrogen 4 5 1 Rotate the chilled water valve to the maximum openness 100 2 Check that the needle valves and exhaust valves on the pipeline are closed If the pressure decreases apply soapy water on the pipes especially pipe joints to check for any leakage If the pressure is stable wrap all pipes and connectors with thermal insulation foam Install a reducing valve at the outlet of the nitrogen c...

Page 8: ...ose the exhaust valve 5 Manually close the chilled water valve Leakage Test with Water 4 7 1 Manually open the chilled water valve 2 Raise the water pressure in the chilled water pipe to 0 8 MPa If no leakage occurs after 30 minutes retain the pressure for 24 hours The expected result is that the pressure drop is less than 0 01 MPa and the pipe does not leak 3 Release the pressure in the pipes and...

Page 9: ... Cable Optional Connecting the T H Sensor Outside the Cabinet 5 2 1 T H sensors outside the cabinet 1 Connect the T H sensor outside the cabinet 2 Set the DIP switch on the T H sensor Model without heating Model with heating ...

Page 10: ...21 ON OFF ON OFF ON OFF Hot aisle temp humid 2 22 OFF ON ON OFF ON OFF Hot aisle temp humid 3 23 ON ON ON OFF ON OFF Hot aisle temp humid 4 24 OFF OFF OFF ON ON OFF Hot aisle temp humid 5 25 ON OFF OFF ON ON OFF Installing a Micro Differential Pressure Sensor 5 3 Connect a pressure inlet tube to the mark and route it to the positive pressure area of the equipment room through the hole atop Ensure ...

Page 11: ...a Water Sensor 5 4 The following figure uses the water sensor as an example A water detection cable can also be connected Model without heating Model with heating Connecting the Teamwork Network Cable and Monitoring Cable 5 5 ...

Page 12: ...RS485 monitoring cascading 10 COM FE port Connects a monitoring communications cable 11 DP port Connects to the display 1 Crimp a network cable PIN Color COM FE Port RS485 Monitoring 4 Blue RS485 5 White and blue RS485 PIN Color FE_1 and FE_2 CAN_IN and CAN_OUT RS485 12V Port COM FE Port FE Monitoring 1 White and orange FE TX RS485 T RS485 HT FE TX 2 Orange FE TX RS485 T RS485 HT FE TX 3 White and...

Page 13: ...ng Protocol CAN Modbus RTU Connect the COM FE port on the main control module of the last smart cooling product in each group to the RS485 port on the host CAN teamwork FE monitoring Networking Teamwork Monitoring Protocol CAN Modbus TCP SNMP Customers can purchase Huawei s switch and NetEco for the monitoring system ...

Page 14: ...onnect the COM FE port on the main control module of the last smart cooling product in each group to the RS485 port on the host MAC_CAN teamwork FE monitoring Networking Teamwork Monitoring Protocol MCA_CAN Modbus TCP SNMP Customers can purchase Huawei s switch and NetEco for the monitoring system ...

Page 15: ...led water connector joints have been wrapped with thermal insulation foam and no metal or hose are exposed Cables are securely connected to the chilled water valve and its actuator Cables to the chilled water valve and its actuator are secured Check that the manual button on the actuator is reset the button bounces up Passed Failed 6 Installation Verification 7 Equipment Power On 1 Users are class...

Page 16: ...and retain default values No for other smart cooling products 4 Teamwork function Indicates whether to disable or enable the teamwork function If disabled a unit operates independently If enabled a unit operates in team with other units 5 Network The networking mode set on the screen must be consistent with the actual networking mode Otherwise the teamwork control function will be unavailable 6 To...

Page 17: ...m log in as the operator user first before modifying parameters Confirm with Huawei before modifying parameters which cannot be modified by the operator user otherwise Huawei will not be liable for any consequences of the modification The following figure shows the flowchart for the first power on If the system has been powered on previously choose Maint Wizard Startup to perform the commissioning...

Page 18: ...n the water in the heat exchanger or take antifreeze measures to avoid frost cracks The password protection function during startup and shutdown has been added Perform operations as required Appendix 1 Precautions Against Adding Glycol For details about adding glycol refer to the FusionCol8000 C210 In room Chilled Water Smart Cooling Product User Manual To prevent glycol solution from corroding pi...

Page 19: ...Huawei Technologies Co Ltd Huawei Industrial Base Bantian Longgang Shenzhen 518129 People s Republic of China www huawei com ...

Reviews: