PDC-(0250, 0400, 0630) DC0384BXA Battery Circuit
Breaker Box
Quick Installation Guide
4 Setting Parameters
Issue 03 (2019-05-20)
Copyright © Huawei Technologies Co., Ltd.
29
Step 2
Set
MUE05A connection
to
Enable
and then set both
BCB connection [OL]
and
Battery
breaker [STA]
to
Enable
.
Figure 4-2
BCB setting
----End
UPS New WebUI
Step 1
Log in to the WebUI and choose
Monitoring > UPS system > Running Parameter > Dry
contact setting
.
The preset passwords for admin and operator on the WebUI are both Changeme.
Step 2
Set
Mue05a connection
to
Enable
and then set both
BCB connection
and
Battery breaker
to
Enable
.