DRH3980A&3909A&3918A&
3918B&3921A&3921B&3926A
Hardware Description
3 DRH Cables
Issue DraftA (2013-08-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd..
10
3.2 DRH PGND Cable
An DRH PGND cable connects an DRH and a ground bar, ensuring the proper grounding of
the DRH. The maximum length of the DRH PGND cable is 8 m (26.25 ft).
Exterior
An DRH PGND cable is green or green and yellow with a cross-sectional area of 16 mm
2
(0.025 in.
2
). This cable has an OT terminal at each end.
cable.
Figure 3-1
PGND cable
(1) OT terminal (M6, 16 mm
2
or 0.025 in.
2
)
(2) OT terminal (M8, 16 mm
2
or 0.025 in.
2
)
If the customer prepares the PGND cable, a copper-core cable with a cross-sectional area of 16 mm
2
(0.025 in.
2
) or larger is recommended.
One OT terminal must be added to each end of the PGND cable onsite.
You can determine the color of the cable and whether to use corresponding two-hole OT terminals
based on local regulations.
Figure 3-2
Two-hole OT terminal
3.3 DRH Power Cable
The DRH power cable is a -48 V DC shielded cable. It feeds -48 V DC power to an DRH. The
default length of an DRH power cable is 50 m (164.04 ft).