Professional humidity switch PLS1000
7.1 T SET
T SET
25.0°C
Factory setting
Here the set-point value for the temperature is set. The value can be changed
with the
keys. When the setting is completed, this is confirmed with the
SET
button. The device will then show the next menu item.
Setting range: -40…120 °C
7.2 T-DIFF KÜHLEN (COOLING)
T-DIFF KÜHLEN
2.0°C
Factory setting
Here the switch-on difference for the „Cooling“ function is set. The value can be
changed with the
keys. When the setting is completed, this is confirmed
with the
SET
button. The device will then show the next menu item.
Setting range: 0.1…15 °C
The relay „Cooling“ (REL K) is switched on if:
Temperature ≥ (T_set + T_diff_cooling)
The relay „Cooling“ (REL K) is switched off when:
Temperature ≤ T_set