lp-181 Rev. 003 Rel. 008 Date 8.21.18
3
NOTE:
If the storage tank is exposed to the following, do not
operate. Immediately call a qualified service technician.
1. Fire
2. Damage
3. Water
Failure to adhere to these guidelines can result in substantial
property damage, severe personal injury, or death.
High heat sources (sources generating heat 100
o
F / 37
o
C or
greater, such as stove pipes, space heaters, etc.) may damage
plastic components of the storage tank as well as plastic vent
pipe materials. Such damages ARE NOT covered by warranty. It is
recommended to keep a minimum clearance of 8” from high heat
sources. Observe heat source manufacturer instructions, as well
as local, state, provincial, and national codes, laws, regulations
and ordinances when installing this storage tank and related
components near high heat sources.
A. When Servicing the Water Heating System
To avoid electric shock, disconnect electrical supply before
performing maintenance.
To avoid severe burns, allow storage tank and associated equipment
to cool before servicing.
B. System Water
Do not use petroleum-based cleaning or sealing compounds in
a water heating system. Gaskets and seals in the system may be
damaged. This can result in substantial property damage.
Do not use “homemade cures” or “patent medicines”. Damage to the
storage tank, substantial property damage, and/or serious personal
injury may result.
C. Freeze Protection
NOTE:
Consider piping and installation when determining tank
location. Place the storage tank as close to the boiler as possible in a
location not prone to freezing.
Failure of the storage tank due to freeze related damage IS NOT
covered by product warranty.
UNCRATING THE STORAGE TANK
- Any claims for damage or
shortage in shipment must be filed immediately against the
transportation company by the consignee.
Households with small children, disabled, or elderly persons may
require a 120
o
F or lower temperature setting to prevent severe
personal injury or death due to scalding.
D. Water Temperature Adjustment
If the storage tank is going to have a set temperature above 120
o
F,
you must use an ASSE 1017 rated mixing valve to avoid severe burns
or death from scalding temperatures.
Part 2 - Prepare the Storage Tank
Remove all sides of the shipping crate to allow the tank to be moved
into its installation location.
COLD WEATHER HANDLING
- If the storage tank has been stored
in a very cold location (BELOW 0
o
F) before installation, handle with
care until the components come to room temperature. Failure to do
so could result in damage to the storage tank.
NOTE:
To save on heating costs and improve energy efficiency keep
the distance between the boiler and storage tank to a minimum
to reduce heat loss from excess piping and keep friction loss at a
minimum. Ensure all piping between the boiler and storage tank is
properly insulated to minimize heat loss.
The storage tank may be located some distance from the boiler
provided the circulator meets flow requirements. The greater the
distance from the boiler to the storage tank the longer the response
will be to a call for hot water.
This storage tank must be installed vertical on a level surface.
NOTE:
In the State of California, the storage tank must be braced,
anchored, or strapped to avoid moving during an earthquake. Contact
local utilities for code requirements in your area. Visit http://www.dsa.
dgs.ca.gov or call 1-916-445-8100 and request instructions.
However, applicable local codes shall govern installation. For residential
storage tanks of a capacity of greater than 52 gallons, consult the local
building jurisdiction for acceptable bracing procedures.
NOTE:
If you do not provide the minimum clearances shown in
Figure 1, it might not be possible to service the storage tank without
removing it from the space.
Do not use this storage tank for anything other than its intended
purpose (as described in this manual). Doing so could result in
property damage and WILL VOID product warranty.
A. Locating the Storage Tank
This storage tank is certified for indoor use only. DO NOT INSTALL
OUTDOORS. Outdoor installations ARE NOT covered by warranty.
Choose a location for the storage tank as centralized to the piping
system as possible. Also, locate the storage tank and domestic water
piping where it will not be exposed to freezing temperatures. All
piping should be insulated. Additionally, place the storage tank so that
the drain, controls, and inlets/outlets are easily accessible.
All water heaters eventually leak. Locate the water heater where any
leakage from the relief valve, related piping, tank, or connections
will not result in damage to surrounding areas or lower floors of the
building. Any water heater should be installed in such a manner that
if it should leak the resulting flow of water will not cause damage
to the area in which it is installed. National Plumbing codes require
a drain pan for any water heater installation. This drain pan should
be sized with a maximum depth of 2”, and a minimum diameter
2” greater than the diameter of the water heater. The drain pan
should empty into an open drain line. This drain line should be
3/4” ID minimum, piped to an open drain. Leakage damages ARE
NOT covered by warranty. Failure to install a drain pan is the sole
responsibility of the owner and/or installer. Reference UPC 2000
(Uniform Plumbing Code) Section 510 - Protection from Damage or
IPC 200 (International Plumbing code) Section 504 - Safety Devices.
Leakage damages ARE NOT covered by warranty.
In addition, water leak detection devices and automatic water
shutoff valves are readily available at plumbing supply houses. IT IS
HIGHLY RECOMMENDED BY THE MANUFACTURER TO INSTALL WATER
LEAK DETECTION DEVICES AND AUTOMATIC SHUTOFF VALVES IN
ANY WATER HEATER INSTALLATION WHERE A LEAKAGE OF WATER
COULD RESULT IN PROPERTY DAMAGES.