
lp-657 Rev. 001 Rel. 000 Date 12.10.18
27
B. Approved Materials for Exhaust Vent and Intake Pipe
•
The exhaust and intake components installed with this boiler must be used for near boiler piping BEFORE transitioning to the
approved materials listed above. DO NOT REMOVE these installed components. Doing so WILL VOID boiler warranty.
•
PVC / CPVC pipe and fittings of the same diameter are considered interchangeable.
•
DO NOT use Foam Core Pipe in any portion of the exhaust piping from this boiler.
•
DO NOT connect PVC/CPVC to Polypropylene without an approved vent connector.
•
Any transition to Polypropylene MUST be done in the vertical within five (5) feet of the appliance.
•
When installing AL29-4C vent piping, install a PVC-to-stainless adapter at the boiler vent connection, and at the termination when
using a PVC termination kit. DO NOT mix AL29-4C piping from different manufacturers unless using adapters specifically designed
for the purpose by the manufacturer.
•
A double wall vent may be used when using stainless steel vent material in a freezing climate.
•
*ABS may be used for air intake applications ONLY. ABS is NOT PERMITTED for use in Canada.
•
Contact the venting material manufacturer if there is any question about the applicability of the proposed venting material.
Failure to follow these directions will result in substantial property damage, severe personal injury, or death.
Table 9 - Approved Materials for Exhaust Vent and Intake Pipe
C. Additional Requirements for Installation in Canada
1. Installations must be made with a vent pipe system certified
to ULC-S636. IPEX is an approved vent manufacturer in Canada
supplying vent material listed to ULC-S636. Additionally, you may
use AL29-4C stainless steel venting to comply with Canadian
requirements.
2. The first three (3) feet of vent pipe from the boiler flue outlet must
be readily accessible for visual inspection.
3. The components of the certified vent system must not be
interchanged with other vent systems or unlisted pipe / fittings.
Cellular foam core piping may be used on air inlet piping
only
.
DO NOT mix components from different venting systems without
proper adapters. The vent system could fail, causing leakage of
flue products into the living space. Use only the approved pipe and
fitting materials, and primer and cement specifically designed for
the material used, as listed in the above table. Failure to do so could
result in property damage, serious injury, or death.
High heat sources (generating heat 100
o
F / 37
o
C or greater, such
as boiler flue pipes, space heaters, etc.) may damage plastic
components of the boiler as well as plastic vent pipe materials. Such
damages ARE NOT covered by warranty. It is recommended to keep
a minimum clearance of 8” from high heat sources. Observe heat
source manufacturer instructions, as well as local, state, provincial,
and national codes, laws, regulations, and ordinances when installing
this boiler and related components near high heat sources.
NOTE:
The use of double-wall vent or insulated material for the
combustion air intake pipe is recommended in cold climates to prevent
the condensation of airborne moisture in the incoming combustion
air.
You must not use “B” vent in an exhaust application. “B” vent is for
intake applications ONLY. Using “B” vent in an exhaust application
will result in serious injury or death.
It is required to insert the provided exhaust and intake screens
into the vent terminations to prevent blockage caused by debris
or birds. Failure to keep terminations clear could result in property
damage, severe personal injury, or death.
Item
Material
Standards for Installation In:
United States
Canada
Pipe and Fittings Approved
for Intake ONLY
ABS*
ANSI/ASTM D2661
NOT PERMITTED
Pipe Approved for
Intake OR Exhaust Vent
PVC Schedule 40/80
ANSI/ASTM D1785
PVC, CPVC, and PP Venting Must
be ULC-S636 Certified. IPEX is an
approved manufacturer in Canada.
PVC-DWV Schedule 40/80
ANSI/ASTM D2665
CPVC Schedule 40/80
ANSI/ASTM F441
Polypropylene
UL-1738 or ULC-S636
Stainless Steel AL29-4C
Certified for Category IV and Direct Vent Appliance Venting
Pipe Fittings
PVC Schedule 40
ANSI/ASTM D2466 or D2665
PVC, CPVC, and PP Venting Must
be ULC-S636 Certified. IPEX is an
approved manufacturer in Canada.
PVC Schedule 80
ANSI/ASTM D2467 or D2665
CPVC Schedule 40
ANSI/ASTM F438
CPVC Schedule 80
ANSI/ASTM F439
Pipe Cement
ABS*
ANSI/ASTM D2235
NOT PERMITTED
PVC
ANSI/ASTM D2564
IPEX System 636 Cements and
Primers
CPVC
ANSI/ASTM F493
Pipe Primer
PVC / CPVC
ASTM F656
Summary of Contents for Elite FT EFT-285
Page 22: ...lp 657 Rev 001 Rel 000 Date 12 10 18 22 Figure 9 Piping Symbol Legend ...
Page 41: ...lp 657 Rev 001 Rel 000 Date 12 10 18 41 Figure 31 Internal Connection Diagram ...
Page 66: ...lp 657 Rev 001 Rel 000 Date 12 10 18 66 Figure 36 Cabinet Replacement Parts ...
Page 69: ...lp 657 Rev 001 Rel 000 Date 12 10 18 69 Maintenance Notes ...