21
LP-520 REV. 5.1.17
Figure 9
– Water Pressure vs. Flow Through the Restrictors – 199W Models
PART 5
–
VENTING
Vent this appliance in accordance with these instructions. Failure to do so will result in property damage, severe personal injury, or
death.
DO NOT mix vent systems or materials unless specifically told to do so in this manual.
DO NOT thermally insulate the exhaust vent or intake pipes.
DO NOT use an electric damper, vent damper, or draft hood with this appliance.
DO NOT locate the exhaust vent or intake pipe terminations where exposed to prevailing winds.
Moisture will be produced by the exhaust vent. Take precautions when determining exhaust vent termination. Moisture may fall from the
vent termination to the ground and turn to ice in freezing conditions. Moisture or ice can produce a hazardous condition.
Exhaust condensate is acidic, and could deteriorate the surface below the exhaust vent termination. Ensure this surface is in good
repair (sealed, painted, etc.) to prevent deterioration.
Pitch the exhaust vent pipe ¼” back to the appliance. This ensures that condensate in the exhaust vent returns to the appliance and
drains properly.
Failure to follow these instructions could result in property damage, severe personal injury, or death.
A. INTAKE PIPE AND EXHAUST VENT GUIDELINES
1. Vent system must be installed in accordance with local codes, or, in absence of local codes, the National Fuel Gas Code, ANSI
Z223.1 / NFPA 54 and/or CSA B149.1, Natural Gas and Propane Installation Code.
2.
For installation in Canada
, installer supplied plastic vent piping must comply with CAN/CGA B149.1 and be certified to the
Standard for Type BH Gas Venting Systems, ULC-S636. Components of this listed system must not be interchanged with other vent
systems or unlisted pipes or fittings. All plastic components and specified primers and glues must be from a single system manufacturer
and must not be intermixed with another system manufacturer’s products. Clean and dry all applicable surfaces before applying
cement.
0
1
2
3
4
5
6
7
8
9
10
11
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
Flo
w
(G
PM)
Pressure (PSI)
199W
No Restrictor
White Restrictor (factory)