background image

LP-436 Rev. 5.20.15

8

Locate the water heater where any leakage from the relief valve, 
related piping, tank, or connections will not result in damage 
to surrounding areas or lower floors of the building. The water 
heater should be located near a floor drain or installed in a drain 
pan. Leakage damages ARE NOT covered by warranty.
Failure  of  the  water  heater  or  components  due  to  incorrect 
operating conditions IS NOT covered by product warranty.

Figure 2 - Minimum Service Clearances

NOTE: 

If you do not provide the minimum clearances shown in 

Figure 2 it might not be possible to service the heater without 
removing it from the space.

B. Minimum Clearances

The  minimum  clearances  from  combustible  materials  for  this 
water heater are: 6” (15.2 cm) from the sides and rear, 24” (61 
cm) from the front, and 18” (45.7 cm) from the top.

C. Combustion and Ventilation Air Supply

In  order  for  the  water  heater  to  operate  properly,  it  must  be 
supplied  with  an  uninterrupted  flow  of  clean  combustion  and 
ventilation air. The area around the water heater must always 
be kept clear so that the flow of combustion and ventilation air 
is not blocked. An inadequate supply of air to the water heater 
will  produce  a  bright  yellow  burner  flame,  causing  sooting  in 
the combustion chamber, on the burners, and in the flue tubes. 
This can result in damage to the water heater and serious bodily 
injury if not corrected.
Combustion and ventilation air requirements are determined by 
the water heater location. Water heaters are installed in either 
open (unconfined) spaces or smaller (confined) spaces, such as 
closets or small rooms.

1. Requirements for Unconfined Spaces

An unconfined space is an area with at least 50 cubic feet for each 
1,000 BTU/H of the total input rating for all gas-fired appliances 
installed  in  that  space.  Water  heaters  installed  in  unconfined 
spaces do not usually require outdoor air to function properly. 
However, in buildings with tight construction (heavy insulation, 
vapor  barriers,  weather  stripping,  etc.),  and  particularly  in 
modern buildings, additional fresh air may need to be provided. 
For  instructions  on  obtaining  additional  air  supply,  see  the 
requirements for confined spaces.

2. Requirements for Confined Spaces

In the US (refer to ANSI Z223.1/NFPA 54)
a. All Air From Inside the Building

The  confined  space  shall  be  provided  with  two  permanent 
openings communicating directly with one or more rooms of 
sufficient volume, so that the combined volume of all spaces 
meets  the  criteria  for  an  unconfined  space. The  total  input 
rating  of  all  gas  appliances  installed  in  the  combined  space 
shall be considered in making this determination.

Each opening shall have a minimum free area of one (1) square 
inch per 1,000 BTU/H (22cm

2

/kW) of the total input rating of 

all gas appliances in the confined space, but not less than one 
hundred (100) square inches (645.16 cm

2

). One opening shall 

commence within six (6) inches (15.2 cm) of the top and one 
within six (6) inches (15.2 cm) of the bottom of the enclosure.

Figure 3 - 

Confined Space - All Air from Inside Building

b. All Air From Outdoors

The  confined  space  shall  be  provided  with  two  permanent 
openings,  one  commencing  within  six  (6)  inches  (15.2  cm) 
of  the  top  and  one  commencing  within  six  (6)  inches  (15.2 
cm)  from  the  bottom  of  the  enclosure. The  openings  shall 
communicate directly or by ducts with the outdoors or spaces 
(crawl or attic) that freely communicate with the outdoors.

1)

  When  communicating  directly  with  the  outdoors,  each 

opening shall have a minimum free area of one (1) square inch 
per 4,000 BTU/H (5.5 cm

2

/kW) of the total input rating of all 

gas appliances in the enclosure. See Figure 4.

When  drawing  combustion  air  from  the  outside  into  the 
mechanical  room,  care  must  be  taken  to  provide  adequate 
freeze protection.

Failure  to  provide  an  adequate  supply  of  fresh  combustion 
air can cause poisonous flue gases to enter the living space, 
resulting in severe personal injury or death.

A  confined  space  is  an  area  where  the  volume  is  less  than 
50 cubic feet for each 1,000 BTU/H of the total input rating 
for  all  gas  appliances  installed  in  that  space. Water  heaters 
installed  in  confined  spaces  require  additional  combustion 
and ventilation air. This can be provided in two ways:

Summary of Contents for CG N65 Series

Page 1: ...l injury or death HTPreservestherighttomakeproductchangesorupdateswithoutnoticeandwillnotbeheldliablefortypographical errors in literature NOTETO CONSUMER PLEASE KEEP ALL INSTRUCTIONS FOR FUTURE REFER...

Page 2: ...CINITY OFTHIS OR ANY OTHER APPLIANCE WHATTO DO IFYOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch Do not use any phone in your building Immediately call your gas supp...

Page 3: ...dividual such as a fire chief fire marshal chief of a fire prevention bureau labor department or health department building official or For the Installer This water heater must be installed by qualifi...

Page 4: ...RSONAL INJURY OR DEATH DO NOT USE THIS WATER HEATER IF ANY PART HAS BEEN SUBMERGED IN WATER Immediately call a qualified service technician The water heater MUST BE replaced if it has been submerged A...

Page 5: ...require a 120oF or lower temperature setting to prevent severe personal injury or death due to scalding F Water Temperature Adjustment If the water heater is going to have a set temperature above 120...

Page 6: ...DS concentration will greatly accelerate lime and scale formation in the hot water system Most high TDS concentrations precipitate out of the water when heated This can generate a scale accumulation t...

Page 7: ...water heater See Figure 13 for proper installation The drain pan should be at least 4 10 2 cm larger than the diameter of the water heater and at least 1 2 5 cm deep providing access to the drain val...

Page 8: ...dern buildings additional fresh air may need to be provided For instructions on obtaining additional air supply see the requirements for confined spaces 2 Requirements for Confined Spaces In the US re...

Page 9: ...for all the appliances installed in that confined space See Figure 7 When ducts are used they shall be of the same cross sectional area as the free area of the openings to which they connect The mini...

Page 10: ...afthood assembly is installed Failure to follow these instructions can result in property damage personal injury or death When installing the water heater make sure the location allows clear viewing o...

Page 11: ...stallation with a TjernlundTM side wall power vent kit See Figure 10 This kit can be installed as part of a new installation or retrofitted onto an existing installation The kit consists of a power ve...

Page 12: ...tally L Clearance above paved sidewalk or paved driveway located on public property 7 2 13 m M Clearance under veranda porch deck or balcony 12 Table 3 Side Wall PowerVentTermination Requirements 1In...

Page 13: ...ssure and or temperature the manufacturer has installed a temperature and pressure relief valve that meets the requirements of the Standard for Relief Valves and Automatic Gas Shut Off Devices for Hot...

Page 14: ...ates or CAN CSA B149 1 NationalGas and Propane InstallationCode in Canada Only new piping with cleanly cut threads may be used The water heater and its gas connection must be leak tested before placin...

Page 15: ...ly manual shut off valve must be closed NOTE Theinputratingoftheapplianceisbasedoninstallation and operation at sea level up to elevations of 2 000 ft Low NOx models are certified to operate to 2 000...

Page 16: ...o disconnecting Verify all wiring connections before relighting the water heater Wiring errors can result in property damage personal injury or death Damages to this product due to improper wiring ARE...

Page 17: ...LP 436 Rev 5 20 15 17 Figure 17 Wiring the Control...

Page 18: ...nections been properly installed and are they leak free Is the water heater full of water Gas Connections Complete Is the gas supplied to the water heater the same type indicated on the water heater r...

Page 19: ...ures at the hot water outlet Always remember to check the hot water coming out of any faucet with your hand before use This will reduce the risk of scalding related injury Figure 18 Thermostat D Out o...

Page 20: ...erly refer to Drafthood Operation G Anode This water heater is equipped with multiple anode rods that are designed to prolong the life of the glass lined tank By the electrolytic action these anodes a...

Page 21: ...ater follow these two easy steps 1 Consult the Troubleshooting Guide in this manual It will guide you to the most common problems experienced with a gas fired water heater The solutions you find liste...

Page 22: ...019 16 Access Door 8800P 018 17 Outlet Nipple 8800P 032 18 Nipple Temperature and Pressure ReliefValve 8800P 033 8800P 034 19 Temperature and Pressure ReliefValve 8800P 035 8800P 036 20 Anode 8800P 03...

Page 23: ...water heater The diagnostic system is designed to give the user or qualified service technician a visual indication of the operational status of the different parts of the water heater s control syste...

Page 24: ...LP 436 Rev 5 20 15 24...

Page 25: ...LP 436 Rev 5 20 15 25...

Page 26: ...LP 436 Rev 5 20 15 26...

Page 27: ...LP 436 Rev 5 20 15 27...

Page 28: ...LP 436 Rev 5 20 15 28...

Page 29: ...OXIDE DETECTORS At the time of installation of the side wall horizontal vented gas fueled equipment the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an...

Page 30: ...TING SYSTEM PROVIDED When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment the instruct...

Page 31: ...at optimum efficiency 2 Maintain all related heating components in good operating condition 3 Use the water heater in an open system with a properly sized and installed thermal expansion tank 4 Use th...

Page 32: ...is denied If all warranty conditions are satisfied HTP will provide replacement parts to the retailer For questions about the coverage of this warranty please contact HTP at the address or phone numbe...

Page 33: ...LP 436 Rev 5 20 15 33 Maintenance Notes...

Page 34: ...f Installation Installation Address Product Name Serial Number s Comments Installer s Code Name Installers Phone Number Signed by Installer Signed by Customer Installation Notes IMPORTANT Customer Ple...

Reviews: