background image

 

 

 

 

LP-362 Rev. 7.30.20 

 

 

 

  

 

 

 

 

 

Figure 7 – Installation of Support Elbow

   

 

Figure 8 – Securing the Support Elbow 

12. Mount the wall plate on the wall of the shaft (Fig. 9). Pay attention to 

the correct slope of 3

o

. The pipe of the support elbow must be in the 

center of the hole in the wallplate. See Fig. 9 for proper installation. 

 

13. Depending on the type of system (single wall or concentric) the 

support elbow can be shortened. For single wall, the length of A (Fig. 9) 

must have a minimum length of 3” (40 mm). For concentric 60/100 end 

80/125, the minimum length of A must be .8” (20 mm). For concentric 

100/150, A must be 1.2” (30 mm). 

 

14. Fix the correct version of the shaft connector to the wall plate (see 

Fig. 9, 1 or 2). 

 

 

 

 

 

15. 

When installing the Polypro to PVC 

adapter, first connect the adapter by 

pushing it onto the Polypro pipe. 

Be 

certain that the arrow on the adapter 

is 

facing up.

 Next, slide the PVC/CPVC 

pipe 

into the adapter. Use a flathead 

screwdriver to tighten the adapter to the 

pipe. 

Once the adapter is connected, be 

certain that it pitches ¼” per foot to 

ensure proper condensate drainage (see 

Figure 10). 

 

 

 

 

Orientation of the Polypro to PVC adapter is critical. Be certain that the arrow on the adapter faces up. Failure 

to ensure correct orientation of the adapter will lead to seal failure and an exhaust gas leak, resulting in 

property damage, severe personal injury, or death. 

Figure 9 – Mounting the Wall Plate

 

Figure 10 – Connecting the Polypro to PVC Adapter

 

Summary of Contents for 8400P-001

Page 1: ...he safety alert symbol indicates a potentially hazardous situation which if not avoided may result in property damage INTRODUCTION This instruction manual is for use only with appliances that have been certified to use a Polypropylene ventilation system Installing any other appliance with this system will result in property damage severe personal injury or death SAFETY CONSIDERATIONS Prior to inst...

Page 2: ...th A APPLICATION The maximum positive pressure of the flexible vent kit is 8 w c The maximum flue gas temperature of the appliance must be not more than 230oF 110oC ULC S636 Class IIC This vent kit must only be used in vertical system designs An existing chimney or chase must be used to route the flexible venting system To prevent condensate from pooling in the vent flex pipe is not to bend more t...

Page 3: ...rned off and the leaks repaired No other appliance may be vented into the same chimney or chase flue with the flexible venting system Failure to heed this warning could result in property damage personal injury or death Plastic venting systems shall not pass through rated fire separations The distance between the point of termination of the system must be 6 2 m or more from the combustion air inle...

Page 4: ... mounting instructions at the end of this manual E INSTALLATION Special notes The flexible liner must be treated carefully at low temperatures 5oC 41oF Check all parts for possible shipping damage Rotate the components slightly to assist assembly Installation procedure for flexible flue liners 1 Determine the required location of the opening in the shaft Ensure the flue access cut out meets the mi...

Page 5: ...tall the liner from the top See Fig 6 10 The flexible liner must be installed from the top of the shaft into the installation room To prevent damage to the liner a second person must guide the liner from the top in the middle of the shaft 11 After installing the required length of liner remove the mounting aid by rotating turn counterclockwise Then attach the rigid flex adapter into the support be...

Page 6: ...orrect version of the shaft connector to the wall plate see Fig 9 1 or 2 15 When installing the Polypro to PVC adapter first connect the adapter by pushing it onto the Polypro pipe Be certain that the arrow on the adapter is facing up Next slide the PVC CPVC pipe into the adapter Use a flathead screwdriver to tighten the adapter to the pipe Once the adapter is connected be certain that it pitches ...

Page 7: ...failure property damage severe personal injury or death 15 At the top of the shaft shorten the flexible liner to the required length and make sure that dimension B in Fig 11 is between 1 6 and 2 4 40 and 60 mm 16 Fit the support cross see Fig 11 1 over the liner and let it rest on the wall of the shaft Mount the seal in the last whole groove of the liner Push the flex rigid adaptor on the liner an...

Page 8: ... connector To assure proper drainage of condensate make sure that the arrow on the transition connector is facing up Make sure that the pipe is fully inserted into the connector before tightening the clamps on either end of the connector to fully secure the pipe on both ends 20 Once connected operate appliance Inspect for leaks and test for proper operation 21 Instruct the owner in proper maintena...

Page 9: ...9 LP 362 Rev 7 30 20 Figure 14 Flex Vent Parts List ...

Reviews: