background image

lp-548 Rev. 000 Rel. 004 Date 1.11.19

10

For example: Send a setpoint of 110

o

F. The formula to use for the interpolation is:

Voltage to be applied =  (Desired setpoint – BMS temp at low analog input) (High voltage – low voltage) + Low voltage

 

 

 

 

(BMS temp at high analog input – BMS temp at low analog input)

From the default values:

Desired setpoint = 110

BMS temp at low analog input = 68

BMS temp at high analog input = 180

High voltage = 10

Low voltage = 1.6

[(110 - 68)(10-1.6)/(180 - 68)] + 1.6 = 4.75 volts

(4.75/10) x 100 = 47.5 

 

48 = 30 Hexadecimal

A value of [00] [30] in hexadecimal would be written to holding register 40003/AV2 to issue a command for a 110

o

F setpoint.

NOTE:

 If your particular BMS supports DECIMAL inputs, then the desired voltage level can be sent directly. In the above example, you would 

send 48 (4.8v) to 40003/AV2.

The holding registers need to be set as follows:

Holding Registers

Definition

Decimal Value

HEX Value

Action

40001 / AV0

Configuration

4

04

Set configuration to read 40002

40003 / AV2

Setpoint

0-100

00-64

Enables CH Demand (00 00 disables demand)

Table 14 - Setting Holding Registers for Setpoint

Register 40003/AV2 needs to receive the 

setpoint command as follows: Acceptable 

range is 0 to 100. Value needs to be greater 

than 15 for the appliance to fire.

When the command is 16, the appliance will 

run with the setpoint controlled by the 925 

menu parameter I12 (MIN BOILER TEMP). 

When the command is 100 the appliance 

will run with the setpoint controlled by the 

600 menu parameter CENTRAL HEAT on 

appliances or the PHOENIX setting in the 

water heater user menu.

If the command value is anywhere between 

16 and 100, the appliance will run at a setpoint 

proportional to the command sent between 

minimum and maximum setpoints.

NOTE: 

To ensure proper operation, resend 

the configuration bits to holding register 

40001 / AV0 prior to issuing a command.

Figure 5 - Setpoint Curve

In this configuration, the appliance is controlled by setting the modulation from 0 – 100%. Rate command will be 0 – 100% of the modulation 

range. All sensors and limiting devices (excluding the 0 – 10 Vdc signal, which will be sent to the MODBUS/BACnet adapter) should be 

hardwired to the correct locations on the appliance.

For this command to function, configure the appliance according to the corresponding row in the following table.

2. Send Firing Rate Command from BMS to Appliance

Appliance

Parameter I16

Parameter I17

Phoenix, Munchkin, MODCON rev2 and earlier

2

2

Elite, Elite Premier, EnduroTi

0-10 Volt

Fan Speed

Table 15 - Send Firing Rate from BMS to Appliance

The holding registers need to be set as follows:

Holding Registers

Definition

Decimal Value

HEX Value

Action

40001 / AV0

Configuration

4

04

Set configuration to read 40003

40003 / AV2

Rate Command

0-100

00-64

Sets Modulation %

Table 16 - Setting Holding Registers for Firing Rate

Parameter

Default Values

Default

Deg C

Deg F

Voltages

Appliance temperature setpoint at low analog input

21

68

1.6

Appliance temperature setpoint at high analog input

82

180

10

Table 13 - 0-10 Volt Temperature Values for Setpoint

Summary of Contents for 7350P-636

Page 1: ...s or to important product information CAUTION used without the safety alert symbol indicates a potentially hazardous situation which if not avoided may result in property damage Table of Contents Part 1 General Information 2 A What s in the Box 2 B Minimum System Requirements 2 C Definitions 2 Part 2 Installation 2 A BMS Wiring Requirements 3 B Jumper Setting 3 Part 3 Communication Configuration 4...

Page 2: ... protocol developed by AEG Modicon Baud Baud Rate Number of data bits transmitted per second bps MSB Most Significant Byte BMS Building Management System RS232 RS232 serial full duplex FDX transmission of data standard EMS Energy Management System RS485 RS485 serial transmission of data standard FDX Full Duplex RTU Remote Terminal Unit HDX Half Duplex PG Industry Standard liquid tight wiring entry...

Page 3: ...S BACnet adapter inside the appliance housing Doing so may affect appliance operation or damage the MODBUS BACnet adapter A BMS Wiring Requirements RS 485 Communication Bus Maximum length 4000 feet Cable specification 24 AWG A B twisted pair and GND shielded with characteristic impedance 120 ohm Maximum load 32 units 32 nodes Wires will be passed through the PG connector on the side of the adapter...

Page 4: ...h the RS485 address of 31 will have a device ID of 600031 NOTE MODBUS must be enabled on the appliance as outlined above for the following parameters to be viewed and changed The BACnet address space is comprised of 256 addresses These are defined as follows Address 255 is a broadcast address The master can send data to address 0 and all followers will process the data Addresses 0 127 are free to ...

Page 5: ... 5 Final Baud Rate Settings E Parity and Stop Bits NOTE This setting only applies to MODBUS operation The BACnet protocol does not utilize parity for communication and this setting will have no effect The parity stop bits parameter of the MODBUS BACnet adapter must be set to match the rest of the devices on the bus Although it is common to set serial devices to use no parity setting the parity to ...

Page 6: ...XCEPT Versa Hydro Alarm output BI 33 1 on 0 off 1 10035 CH pump 1 N A BI 34 1 on 0 off 1 10036 DHW pump 1 N A BI 35 1 on 0 off 1 10038 Gas valve 1 Gas valve BI 37 1 on 0 off 1 10039 Sys pump N A BI 38 1 on 0 off 1 10049 Boiler 1 Run same as 11118 Run status BI 48 1 on 0 off 1 10050 Boiler 2 Run same as 10023 N A BI 49 1 on 0 off 1 10051 Boiler 3 Run N A BI 50 1 on 0 off 1 10052 Boiler 4 Run N A BI...

Page 7: ...utlet 3 N A AI 25 Deg F 0 1 30027 Boiler 3 Firing Rate N A AI 26 1 30028 Boiler 3 Status N A AI 27 N A 1 30029 Boiler 3 Lockout N A AI 28 N A 1 30030 Boiler Outlet 4 N A AI 29 Deg F 0 1 30031 Boiler 4 Firing Rate N A AI 30 1 30032 Boiler 4 Status N A AI 31 N A 1 30033 Boiler 4 Lockout N A AI 32 N A 1 30034 Boiler Outlet 5 N A AI 33 Deg F 0 1 30035 Boiler 5 Firing Rate N A AI 34 1 30036 Boiler 5 St...

Page 8: ...Table 8 MODBUS and BACnet Memory Map Only Valid Valves During Heating Cycle Address 40001 AV0 contains configuration bits sent from the BMS to the appliance These bits tell the appliance to use its own internal inputs or inputs from the BMS When a bit is set to 1 the appliance will ignore the corresponding value contained internally and expect the BMS to write that value into the holding registers...

Page 9: ...rs Definition Decimal Value HEX Value Action 40001 AV0 Configuration 3 0011 Set configuration to read 40002 40002 AV1 Coils 1 0001 Enables CH Demand 00 00 disables demand boilers only 40002 AV1 Coils 16 0010 Enables DHW demand on appliance 00 00 disables demand 40002 AV1 Coils 17 0011 Enables both CH and DHW demand DHW demand will have priority Table 10 Example 1 Holding Registers Definition Decim...

Page 10: ...with the setpoint controlled by the 600 menu parameter CENTRAL HEAT on appliances or the PHOENIX setting in the water heater user menu If the command value is anywhere between 16 and 100 the appliance will run at a setpoint proportional to the command sent between minimum and maximum setpoints NOTE To ensure proper operation resend the configuration bits to holding register 40001 AV0 prior to issu...

Page 11: ... the typical installation with a hot water generator in close proximity to the appliance with the tank thermostat or tank temperature sensor wired to the terminal strip or Customer Connection Board of the appliance DHW with Remote Control This installation may or may not have the hot water generator in close proximity to the appliance Its sensors and thermostat values are only available through th...

Page 12: ... No Burner Control Communication 0 5 seconds on 1 5 seconds off No MODBUS BACnet Communication 1 5 seconds on 0 5 seconds off Figure 7 MODBUS BACnet Diagnostic LEDs B Physical Layer 1 Adapter and Serial Port a Ensure adapter is plugged into the correct four pin connector i It plugs into the WHITE connector on the BIC 926 control ii It plugs into the BLACK connector on the BIC 928 control C Communi...

Page 13: ...19 Water Low 2 34 None 5 Blocking Temperature 20 Water High 2 35 Service Pump 6 DHW Function Internal 21 CH On Off Thermostat 40 Lockout 7 DHW Function Internal 22 CH Zone Demand 51 Frost Protection Pump 8 DHW Indirect 23 CH Cascade Demand 52 Frost Protection Burner 9 DHW Direct 24 CH Pool Demand 60 Summer Kick 10 DHW Phoenix 25 CH 61 Save EEPROM Blocking 11 DHW Spa 26 CH 96 Running 12 DHW 27 CH 1...

Page 14: ...ing 186 ECS7 Temperature Lockout 233 F09 No Flame After Ignition 190 F05 S1 Maximum Temperature 235 APS Stuck Closed 191 F06 S2 Maximum Temperature 236 APS Stuck Open 192 S1 Shorted 237 F11 False Flame 193 F02 S1 Interrupted 239 F01 Safety Thermostat Open 194 S2 Shorted 240 F00 Flue Thermostat Open 195 S2 Interrupted 241 External LWCO 196 Low Water Lockout 243 Gas Pressure 197 Flue Sensor Shorted ...

Page 15: ...ty Wizard http www htproducts com Warranty Wizard html to check warranty eligibility You may also contact HTP Technical Support at 1 800 323 9651 for questions or assistance Warranty coverage requires review and approval of the issue with HTP Technical Support or through the Warranty Wizard prior to a full unit replacement Any claim for warranty reimbursement will be rejected if prior approval fro...

Page 16: ...lp 548 Rev 000 Rel 004 Date 1 11 19 16 Installation and Maintenance Notes ...

Reviews: