VEGA74
EN - 53
Three-phase 3-wires
3
-Y Open
,
3
-2El. ½, 1
-CentralPoint
– for USA systems
EN50160
Description
Description
System type:
Not modified
Frequency:
Not modified
Clamp type:
Not modified
Full scale clamp:
Not modified
TV ratio:
Not modified
Start recording:
Not modified
Stop recording:
Not modified
Aggregation time:
10min
Harmonic recording:
Selected
Voltage anomalies recording:
Selected
Reference voltage anomalies (Vn)
Not modified
High threshold limit for voltage anomalies:
10%Vn
Low threshold limit for voltage anomalies:
10%Vn
Selected voltage:
V1,V2,V12
Voltage harmonics
THD%,DC,01,02… 49
Voltage unbalance:
Not selected
Voltage frequency::
Selected
Selected current
Not selected
Selected powers
Not selected
Table 10: List of standard parameters saved in a EN50160 typical configuration
HARM.
Description
Description
System type:
Not modified
Frequency:
Not modified
Clamp type:
Not modified
Full scale clamp:
Not modified
TV ratio:
Not modified
Start recording:
Not modified
Stop recording:
Not modified
Aggregation time:
10min
Voltage anomalies recording:
Selected
Reference voltage anomalies (Vn)
Not modified
High threshold limit for voltage anomalies:
Not modified
Low threshold limit for voltage anomalies:
Not modified
Harmonic recording
Selected
Selected voltage:
V1,V2,V12
Voltage harmonics
THD%,DC,01,02… 49
Voltage unbalance:
Not selected
Voltage frequency::
Selected
Selected current
I1,I2,In
Current harmonics:
THD%,DC,01,02… 49
Powers, Energie, power factors
Not selected
Table 11: List of parameters saved in HARMONICS typical configuration