Fifth configuration is the silence state of the device. For input devices, it is not shown.
For output devices, it means that if the device will deactivate when Silence Alarm key is
pressed or will keep active even if Silence Alarm key is pressed. To change it, highlight it
with arrow keys and press 0 key. If X symbol appears in front of it, this means that the device
will deactivate with silence alarm state. If X symbol does not appear in front of the event, this
means that the device will keep active with silence alarm state.
Sixth configuration is disabled state of the device. For input devices, it means that if the
device will trigger its event when activated, or will do nothing whatever is activated or not.
For output devices, it means that if the device will be function or not regardless of the current
panel state. To change it, highlight it with arrow keys and press 0 key. If X symbol appears in
front of it, this means that the device will be disabled and not working. If X symbol does not
appear in front of it, this means that the device will be working normally. If disabled is active,
after saving, general disabled LED will be on.
Seventh configuration is delay value. It is only shown for output devices and not shown
for input devices. It is used to postpone the output device trigger to a defined amount. The
number represents number of half minutes of delay. For example, if value is 3, so the delay
value is 1.5 minutes. If value is 12, so the delay value is 6 minutes. Minimum value is 0
which means that no delay for this output device and it will trigger directly when at least one
of its selected events is active. Maximum value is 14 which mean that maximum delay is 7
minutes. To change the delay value, highlight it with arrow keys and directly enter the new
delay value. A new small window appears beside the last delay value. Press ENTER key after
entering the new delay value. If value is accepted, it will be shown. If value is wrong, X
symbol appears beside the wrong value. While entering the new delay value, press EXIT key
to cancel entering a new delay value.
Eighth configuration is group number. It is exactly same as on board sounder, relay and
aux. power for output devices and same as on board input for input devices. To change the
group value, highlight it with arrow keys and directly enter the new group value. A new small
window appears beside the last group value. Press ENTER key after entering the new group
value. If value is accepted, it will be shown. If value is wrong, X symbol appears beside the
wrong value. While entering the new group value, press EXIT key to cancel entering a new
group value.
Ninth configuration is zone number. It is used to attach the device to one software zone.
To change the zone number, highlight it with arrow keys and directly enter the new zone
number. A new small window appears beside the last zone number. Zone range is from 0 to
250. Press ENTER key after entering the new zone number. If value is accepted, it will be
shown. If value is wrong, X symbol appears beside the wrong value. While entering the new
zone number, press EXIT key to cancel entering a new zone number.
After finishing updates of configuration, enable key must be on to save the new values.
Press ENTER key. If panel is at access level 3, new data will be saved directly. If panel is at
access level 2, window appears to enter access level 3 password to proceed with saving.