HRW HPD0460MR V402 Manual 150622.docx E. & O. E. / Subject to change without notice
Page 7 of 32
U16 Registers
Float32 Registers
Prio Set Registers
Point
Block
Modbus Type
Integer
IEEE Floating Point
Integer
77
PB 1
Holding Register
77
1154
577
78
PB 2
Holding Register
78
1156
578
79
PB 3
Holding Register
79
1158
579
80
PB 4
Holding Register
80
1160
580
81
PB 5
Holding Register
81
1162
581
82
PB 6
Holding Register
82
1164
582
83
PB 7
Holding Register
83
1166
583
84
PB 8
Holding Register
84
1168
584
85
IntTm 1 Holding Register
85
1170
585
86
IntTm 2 Holding Register
86
1172
586
87
IntTm 3 Holding Register
87
1174
587
88
IntTm 4 Holding Register
88
1176
588
89
IntTm 5 Holding Register
89
1178
589
90
IntTm 6 Holding Register
90
1180
590
91
IntTm 7 Holding Register
91
1182
591
92
IntTm 8 Holding Register
92
1184
592
Priority Levels
A priority level is possible for each register to enable local or master override, and setting of start-up
defaults.
Registers are Null priority by default, signified by a value of 17, read in the 500’s register range
Manual commands via terminal mode operate at prio. level 9 and are remembered after a
power reset if written (W) during terminal mode
In terminal mode, Release (R) of a manual results in a register reverting to Null priority
Commands from the network are at prio. 8
Setting a point’s priority to a value of 0 (zero) will Write the point’s current value as the start-up
default
Setting a point’s priority to a value from 1…7 will lock the point’s current value so that it cannot
be changed
Setting a point’s priority to Null (17) will unlock the point so future changes to the point’s value
may be made
Example, based on point 45, used as a temperature set point:
Change set point to a value of 22.5 °C
o
1090=22.5
o
Being an analogue value we have used the IEEE Floating Point register range, based
on the formula 45 x 2 +1000 = 1090
Write current value as a start up default
o
545=0
Lock current value
o
545=1
Release current value for future change
o
545=17