Technical Data
Inputs/Outputs
4 DI, local user interfaces
4 DI, navigation buttons
6 DO
2 DO, local user interfaces
1 UI, local °C
3 UI
3 AO, local user interfaces
Sensor/Transmitter Wiring
Network Wiring
Comms Speed
RS485 Driver
Power Supply
Conformity & approvals
Operating Temperature Range
Storage Temperature Range
Humidity Range
Dimensions
LCD
- DI1…4 user programmable buttons onboard
- DI5…8 fixed functionality, display navigation & setting buttons onboard
- DO1…DO6: 24Vac, 3A in-rush, 300mA holding max., minimum load
10mA
- DO7…DO8: Fixed functionality, LED1… LED2; user programmable on, off
or flashing
- UI1: NTC 10kΩ internal temperature sensor
- UI2: NTC 10kΩ or DI
- UI3…UI4: NTC thermistor 10kΩ, 100kΩ, DI, 0-10Vdc 0.01 Volt
resolution, 4…20mA, 0.016mA resolution (requires 18…28Vdc loop
power supply)
- AO1…2 Fixed functionality, LED3… LED4; user programmable on, off or
flashing
- AO3 Fixed functionality, Audible beeper; user programmable on, off or
intermittent beep
Shielded twisted pair (shield grounded)
Belden 9841 low capacitance twisted pair for RS485 networks (b
foil shield, shield continuous throughout the network and grounded at
network origin)
RS485 - 2400, 4800, 9600, 19200, 38400, 57600, 76800 baud
Isolated 1/8
th
load, 256 nodes over max. 1.2km without repeater
24Vac, 50/60 Hz, max. 5VA without DO load
50VA MAX. when DO’s supplied via the device’s 24Vac terminals and fully
loaded @ max. 300mA / DO
UL 916
CAN/CSA C22.2 #205-M1983
FCC Part 15 Subpart B Class B
EN 55022, EN 55024, EN 61000-3-2, EN 61000-3-3
0…50ºC (32…122ºF)
-5…75ºC (-40…167ºF)
10…95%rH (non-condensing)
122mm H x 92mm L x 29mm D
8 line dot matrix
62mm x 29mm visible
54mm x 24mm usable