
11
881629-001
ENGLISH
2. Presentation
2.5 Display functions
Press the Enter (
) button to activate the menu options. Use the two middle buttons ( and ) to scroll
through the menu structure. Press the Enter (
) button to select an option. Press the
button to cancel
or return to the previous menu.
Menu map for display functions
Main Menu
Submenu
Display information or menu function
Measurements
Load W VA / Load A pf / Output V Hz / Input V Hz /
Battery V min / Efficiency / Power usage
Control
Load Segments
Group 1: ON / OFF
Group 2: ON / OFF
These commands override user settings for load segments.
Start battery test
Starts a manual battery test
Reset fault state
Clears active faults (UPS restart required)
Restore factory settings Returns all settings to original values
Reset power usage
Clears power usage measurements
Settings
Local settings
Sets product general parameters
Input / output settings
Sets input and output parameters
ON / OFF settings
Sets ON / OFF conditions
Battery settings
Sets battery configuration
Fault log
Displays event log or alarms
Identification
UPS Type / Part Number / Serial Number / Firmware release /
Com card address
2.6 User settings
The following table displays the options that can be changed by the user.
Description
Available settings
Default settings
Local Settings
Language
[English] [Français] [Deutsch]
[Italiano] [Português] [Español]
[
Русский
]
Menus, status, notices and alarms,
UPS fault, Event Log data and
settings are in all supported
languages.
English
User selectable when
UPS is powered for the
first time.
LCD settings
Modify LCD screen brightness and
contrast to adapt to room light
conditions.
Audible alarm
Mode
[Enabled] [Disabled on battery] [Always
disabled]
Allows you to enable or disable the
audio alarm if an alarm occurs.
Enabled
Level
[High] [Low]
Allows you to set the audio alarm level
if an alarm occurs.
Low
In/Out Settings
Output voltage
[100 V] [120 V] [125 V]
On INTL model: [200 V] [208 V]
[220 V] [230 V] [240 V]
User selectable when
UPS is
powered for the first
time.
Input thresholds
[Normal mode] [Extended mode]
Extended mode reduces lower input
voltage to 70 V before UPS transfers
to battery.
This can be used if the load can
withstand low voltage supply.
Normal mode
Sensitivity
[High] [Low]
High: For sensitive equipment. The
UPS transfers to battery when AC
utility conditions are poor.
Low: For equipment that can
withstand poor utility conditions.
The UPS does not transfer to battery
when AC utility conditions are poor.
High
Load segments - Auto
start delay
[No Delay] [1 s] [2 s]…[65354 s]
The connected load is powered after
the specified delay.
Group 1: 3 s
Group 2: 6 s