Installation Instructions
11
universal port module kit installation instructions
If an event code 501 does not display in the log, go to MAP 0000: Start MAP of
the hp StorageWorks director 2/64 service manual,
to isolate the problem.
11. At the Hardware View, double-click the graphic representing the replacement
card to open the Port Card View. At the Port Card View:
a.
Ensure no alert symbols display that indicate a failure (yellow triangle or red
diamond).
b.
Verify UPM card information (FRU name, position, and state) is correct.
If a problem is indicated, go to MAP 0000: Start MAP of the hp StorageWorks
director 2/64 service manual to isolate the problem.
12. Close and lock the equipment cabinet door.
13. Initiate communication to the UPM card and set the card online as needed. For
instructions, refer to
of the hp StorageWorks director 2/64
service manual,
A6534-96022/AA-RS2EA-TE
.
Miscellaneous Procedures
The following are miscellaneous procedures that you can perform on your UPM card.
External Loopback Test
To perform an external loopback test for a single port or a UPM card (four ports):
1. If the UPM card is currently being used in a fabric, then notify storage users on
the fabric that a disruptive external loopback test will be performed on a port or
UPM card, and the fiber optic cable or cables will be disconnected. Ensure the
system administrator queues Fibre Channel frame traffic through the port or UPM
card and sets attached devices offline.
NOTE: At the start of the loopback test, the port or UPM card can be online, offline, blocked, or
unblocked.
2. At the HA-Fabric Manager server, open the ha-fabric manager application. The
Product View displays.
3. Double-click the icon representing the director for which the loopback test will be
performed. The Hardware View for the selected director displays.