System Unit
System Unit
System Unit
System Unit
Dimensions
Dimensions
Dimensions
Dimensions (H x W x D)
(with bezel)
1.70 x 16.78 x 27.75 in (4.32 x 42.62 x 70.49 cm)
Weight
Weight
Weight
Weight
(approximate)
Maximum
(all hard drives, power
supplies, and processors
installed)
37 lb (16.78 kg)
Minimum
(one hard drive, power
supply, and processor
installed)
27.5 lb (12.47 kg)
Input Requirements
Input Requirements
Input Requirements
Input Requirements
(per power supply)
Rated Line Voltage
90 - 132 VAC,
180 - 264 VAC
Rated Input Current
8.5 A (at 100 VAC),
4.2 A (at 200 VAC)
Rated Input Frequency
47 to 63 Hz
Rated Input Power
854 W (at 100 VAC),
844 W (at 200 VAC)
BTU Rating
BTU Rating
BTU Rating
BTU Rating
Maximum
2916 BTU/hr (at 100 VAC),
2882 BTU/hr (at 200 VAC)
Power Specifications
Power Specifications
Power Specifications
Power Specifications
To review typical system power ratings use the Power Calculator which is
available via the online tool located at URL:
http://h30099.www3.hp.com/configurator/calc/
Power%20Calculator%20Catalog.xls
- Click on the system of interest. Example: DL360 G5
- Follow the instructions of the next screens.
Power Supply Output
Power Supply Output
Power Supply Output
Power Supply Output
(per power supply)
Rated Steady-State Power 700 W (at 100 VAC),
700 W (at 200 VAC)
Maximum Peak Power
700 W (at 100 VAC),
700 W (at 200 VAC)
System Inlet Temperature
System Inlet Temperature
System Inlet Temperature
System Inlet Temperature Operating
10° to 35°C (50° to 95°F) at sea level with an
altitude derating of 1.0°C per every 305 m
(1.8°F per every 1000 ft) above sea level to a
maximum of 3050 m (10,000 ft), no direct
sustained sunlight. Maximum rate of change is
10°C/hr (18°F/hr). The upper limit may be
limited by the type and number of options
installed.
System performance may be reduced if
operating with a fan fault or above 30°C (86°F).
Non-operating
-30° to 60°C (-22° to 140°F). Maximum rate of
change is 20°C/hr (36°F/hr).
Relative Humidity
Relative Humidity
Relative Humidity
Relative Humidity
(non-condensing)
Operating
10 to 90% relative humidity (Rh), 28°C (82.4°F)
maximum wet bulb temperature, non-
condensing.
Non-operating
5 to 95% relative humidity (Rh), 38.7°C
(101.7°F) maximum wet bulb temperature, non-
condensing.
QuickSpecs
HP ProLiant DL360 Generation 5 (G5)
HP ProLiant DL360 Generation 5 (G5)
HP ProLiant DL360 Generation 5 (G5)
HP ProLiant DL360 Generation 5 (G5)
Technical Specifications
DA - 12476 North America — Version 27 — September 10, 2007
Page 40