HP Rack Series
Rack 10000 G2 Series
HP 10642 G2 1200mm deep Shock Rack
AF092A
HP 10647 G2 1200mm deep Shock Rack
AF094A
NOTE:
For additional information regarding Rack Cabinets, please see the following
URL:
http://www.hp.com/go/rackandpower
.
HP Rack Options
HP USB Keyboard and Mouse
HP USB BFR with PVC Free US Keyboard/Mouse Kit
631341-B21
HP USB BFR with PVC Free CN Keyboard/Mouse Kit
631364-B21
NOTE:
Please see the QuickSpecs for Technical Specifications and additional
information:
http://h18000.www1.hp.com/products/quickspecs/13972_na/13972_na.html
HP KVM Switches
HP Server Console 0x2x8 Port Analog Switch
AF616A
HP Server Console 0x2x16 Port Analog Switch
AF617A
NOTE:
Please see the QuickSpecs for Technical Specifications and additional
information:
http://h18000.www1.hp.com/products/quickspecs/11834_na/11834_na.html
HP 1x4 USB/PS2 KVM Console Switch
AF611A
Rack 10000 G2 series Cabinets
The increasing power of new high-performance processor technology requires
increased cooling efficiency for rack-mounted servers. The 10000 G2 Series Racks
provide enhanced airflow for maximum cooling, allowing these racks to be fully loaded
with servers using the latest processors.
CAUTION:
If a third-party rack is used, observe the following additional requirements to
ensure adequate airflow and to prevent damage to the equipment:
Front and rear doors: If your 42U server rack includes closing front and rear doors, you
must allow 5,350 sq cm (830 square inches) of hole evenly distributed from top to
bottom to permit adequate airflow (equivalent to the required 64 percent open area for
ventilation).
Side: The clearance between the installed rack component and the side panels of the
rack must be a minimum of 7 cm (2.75 inches)
CAUTION:
Always use blanking panels to fill all remaining empty front panel U-spaces in
the rack. This arrangement ensures proper airflow. Using a rack without blanking
panels results in improper cooling that can lead to thermal damage.
HP ProLiant DL160 G6 models have fixed rails which provide support for racks with
round mounting holes and tool-free support for racks with square mounting holes
(including Compaq/HP 7000, 9000, 10000 and HP series), with an adjustment range of
24" - 36"
NOTE:
For additional information regarding Rack Cabinets and Telco Rack support,
please see the following URL:
www.hp.com/go/rackandpower
.
QuickSpecs
HP ProLiant DL160 Generation 6 (G6)
Additional Options
DA - 13247 North America — Version 59 — September 24, 2012
Page 35