Customer Provided Part
Customer Provided Part
Customer Provided Part
Customer Provided Part
PDCA Product
PDCA Product
PDCA Product
PDCA Product
Number
Number
Number
Number
Attached Power
Attached Power
Attached Power
Attached Power
Cord
Cord
Cord
Cord
Attached Plug
Attached Plug
Attached Plug
Attached Plug
In Line Connector
In Line Connector
In Line Connector
In Line Connector
Panel Mount
Panel Mount
Panel Mount
Panel Mount
Receptacle
Receptacle
Receptacle
Receptacle
A5800A Option
006
OLFLEX 190 (PN
600804), four-
conductor, 6-AWG
(16 mm
2
), 600-
Volt, 60-Amp, 90-
degree C, UL, and
CSA approved,
conforms to CE
directives GN/YW
ground wire.
Mennekes ME
460P9 3-phase, 4-
wire, 60-Amp, 250-
Volt, UL-approved.
Color blue, IEC
309-1, IEC 309-1,
grounded at 3:00
o'clock.
Mennekes ME
460C9 3-phase,
4-wire, 60-amp,
250-Volt, UL-
approved. Color
blue, IEC 309-1,
IEC 309-1,
grounded at 9:00
o'clock.
a
Mennekes ME
460R9 3 phase,
4-wire, 60-amp,
250-Volt,
UL-approved. Color
blue, IEC 309-1,
IEC 309-1,
grounded at 9:00
o'clock.
b
A5800A Option
007
Five conductors,
10-AWG (6 mm
2
),
450/475-Volt, 32-
Amp, <HAR>
European wire
cordage, GN/YW
ground wire.
Mennekes ME
532P6-14 3-phase,
5-wire, 32-Amp,
450/475-volt, VDE-
certified, color red,
IEC 309-1, IEC
309-2, grounded at
6:00 o'clock.
Mennekes ME
532C6 16 3-phase,
5-wire, 32-Amp,
450/475-Volt, VDE-
certified, color red,
IEC 309-1, IEC
309-2, grounded at
6:00 o'clock.
c
Mennekes
ME532R6 1276 3-
phase, 5-wire, 32-
Amp, 450/475-
Volt, VDE- certified,
color red, IEC 309-
1, IEC 309-2,
grounded at 6:00
o'clock.
b
a. In-line connector is available from HP by purchasing A6440A, Option 401.
b. Panel mount receptacles must be purchased by the customer from a local Mennekes supplier.
c. In-line connector is available from HP by purchasing A6440A, Option 501.
NOTE:
NOTE:
NOTE:
NOTE: A qualified electrician must wire the PDCA in line connector to site power using copper wire and
in compliance with all local codes.
Input Requirements
Input Requirements
Input Requirements
Input Requirements
Reference the Site Preparation Guide for detailed power configuration requirements.
Requirements
Requirements
Requirements
Requirements
Value
Value
Value
Value
Conditions/Comments
Conditions/Comments
Conditions/Comments
Conditions/Comments
Nominal Input Voltage (VAC rms) 200/208/220/230/240
Input Voltage Range (VAC rms)
200-240
Auto-selecting. Measure at input
terminals
Frequency Range (Hz)
50/60
Number of Phases
3
3-phase 5-wire with power cord;
3-phase 4-wire with power cord
Maximum Input Current (A rms),
3-Phase 5-wire
20
3-phase source with a source
voltage of 220 VAC measured
phase to neutral
Maximum Input Current (A rms),
3-Phase 4-wire
40
3-phase source with a source
voltage of either 208 VAC or 230
VAC measured phase to phase
Maximum Inrush Current (A peak) 90
Circuit Breaker Rating (A),
3-Phase 5-wire
25 A
Per phase
Circuit Breaker Rating (A),
3-Phase 4-wire
45 A
Per phase
Power Factor Correction
0.95 minimum
QuickSpecs
HP Integrity Superdome Servers 16-socket, 32-socket,
HP Integrity Superdome Servers 16-socket, 32-socket,
HP Integrity Superdome Servers 16-socket, 32-socket,
HP Integrity Superdome Servers 16-socket, 32-socket,
and 64-socket
and 64-socket
and 64-socket
and 64-socket
Configuration
DA - 11717 Worldwide — Version 20 — May 3, 2005