the resulting heat from the cabinet. The fans within the power supply will operate at full speed
during standby.
Typical HP Integrity rx8640 Server Power Dissipation and Cooling
Table 2-10
provides calculations for the rx8640 configurations as described in the table.
Table 2-10 Typical HP Integrity rx8640 Server Configurations
Typical
Cooling
Typical
Power
Bulk Power
Supplies
Core
I/O
Hard Disk
Drives
DVDs
PCI Cards
(assumes 10W
each)
Memory
per Cell
Board
Cell
Board
BTU/hr
Watts
Qty
Qty
Qty
Qty
Qty
GBytes
Qty
13257
3883
6
2
4
2
16
32
4
12383
3627
6
2
4
2
16
16
4
11672
3419
6
2
2
0
8
8
4
9385
2749
4
2
4
2
16
32
2
8402
2461
4
2
2
0
8
16
2
8183
2397
4
2
2
0
8
8
2
6463
1893
3
1
1
0
8
8
1
The air-conditioning data in
Table 2-10
are derived using the following equations.
•
Watts x (0.860) = kcal/hour
•
Watts x (3.414) = Btu/hour
•
BTU/hour divided by 12,000 = tons of refrigeration required
NOTE:
When determining power requirements, you must consider any peripheral equipment
that will be installed during initial installation or as a later update. Refer to the applicable
documentation for such devices to determine the power and air-conditioning that is required to
support these devices.
Typical HP 9000 rp8440 Server Power Dissipation and Cooling
Table 2-11
provides calculations for the rp8440 configurations as described in the table.
Table 2-11 Typical HP 9000 rp8440 Server Configurations
Typical
Cooling
Typical
Power
Bulk Power
Supplies
Core
I/O
Hard Disk
Drives
DVDs
PCI Cards
(assumes 10W
each)
Memory
per Cell
Board
Cell
Board
BTU/hr
Watts
Qty
Qty
Qty
Qty
Qty
GBytes
Qty
12936
3789
6
2
4
2
16
32
4
12062
3533
6
2
4
2
16
16
4
11352
3325
6
2
2
0
8
8
4
9225
2702
4
2
4
2
16
32
2
8241
2414
4
2
2
0
8
16
2
8023
2350
4
2
2
0
8
8
2
6463
1893
3
1
1
0
8
8
1
Environmental Specifications
39