background image

1-7

Before applying power to the supply, check the label on the
heat sink to make certain that the supply's line voltage option
agrees with the line voltage to be used. If the option does not
correspond to your line voltage, refer to paragraph "LINE
VOLTAGE OPTION CONVERSION" in the service section
before applying power.

TURN -ON CHECKOUT PROCEDURE

a.

Connect line cord to power source and turn LINE 
switch  

on. 

 

b.

Push +6V METER switch 

 and, with no load con-

nected, vary +6V VOLTAGE control 

 over its range 

and check that the voltmeter responds to the control 
setting and the ammeter indicates zero.

c.

Set the +6V VOLTAGE control to 6 volts and short the 
+6V output terminal 

 to COM (common) terminal 

 with an insulated test lead. The ammeter should 

indicate a short-circuit output current of approximately 
1.0 A. Remove the short from the output terminals.

d.

Push the +20V METER switch 

 and turn Tracking 

Ratio control 

 fully clockwise to the Fixed position. 

With no load connected, vary ±20V VOLTAGE control

 over its range and check that the voltmeter 

responds to the control setting and the ammeter indi-
cates zero.

e.

Set the ±20V VOLTAGE control 

 to 20 volts and 

short the +20V output terminal 

 to the COM terminal

 with an insulated test lead. The ammeter should 

indicate a short-circuit output current of 0.55 A ± 5%. 
Remove the short from the output terminals.

f.

Repeat steps (d) and (e) for -20 V output.

g.

Adjust the +20V output to 20 volts. Then push -20V 
METER switch and check the effect of the Tracking 
Ratio control on the voltage of  the -20V  output.  The -
20V output should be adjustable from less than 0.5 
volts to a maximum of 19 to 21 volts.

If this brief checkout procedure or later use of the supply
reveals a possible malfunction, see the service information
section for detailed test, troubleshooting, and adjustment pro-
cedures.

OPERATION

This power supply can be operated individually or in parallel
or series with another supply (see Parallel and Series Opera-
tion paragraphs). All output terminals are isolated from
ground. The ±20V and +6V outputs use a single common out-
put terminal. This common (COM) terminal or any one of the
other output terminals may be grounded to the chassis at the
front panel ground terminal (

 in Figure 2), or all outputs may

be left floating. Loads can be connected separately between
each of the 0 to ±20V output terminals and the COM terminal,
or between the -20V and the +20V terminals for a 0 to 40V
output. Each output voltage or current can be quickly selected
for monitoring with the push-button meter switches. To moni-

tor the 0 to 40V output voltage, add the voltmeter readings of
the +20V and -20V output and use either the +20V or the -
20V meter to measure the current.

Tracking Ratio Control

With the Tracking Ratio control in the Fixed position, the volt-
age of the -20V supply tracks that of the +20V supply within
1% for convenience in varying the symmetrical voltages
needed by operational amplifiers and other circuits using bal-
anced positive and negative inputs. 

Turn the Tracking Ratio control counter clockwise out of the
Fixed position to set the voltage of the -20V supply lower than
that of the +20V supply. The negative supply can be set from
a minimum of less than 0.5 volts to a maximum within 5% of
the +20V supply's output. Once this is done, the ±20V voltage
control still controls both outputs and maintains a constant
ratio between their voltages.

Overload Protection Circuits

±20-Volt Current Limit. The +20V and -20V outputs are indi-
vidually protected against overload or short circuit damage by
separate current limit circuits to limit the output current to 0.55
A ± 5%. (This is 110% of the maximum rated output.) If a sin-
gle load is connected between the +20V and -20V outputs,
the circuit set for the lesser current limit will limit the output.
No deterioration of supply performance occurs if the output
current remains below the current limit setting. 

+6V Current Foldback. The overload and short-circuit pro-
tection circuit for the +6V output reduces the output current
limit as the output terminal voltage decreases. (The operating
region of the +6V output is enclosed by heavy lines in Figure
4.) The maximum rated output current is 2.5 A and the current
limit is factory-adjusted to operate at 2.75 A ± 5% when the
output is 6 volts. At lower output voltages, the circuit reduces
the maximum obtainable output current linearly until 1 A ±
15% flows when the output is shorted. The short-circuit cur-
rent can not be adjusted.

During the actual operation of the ±20V and +6V outputs, if a
load change causes the current limit to be exceeded, the OL
LED is lighted. If overload conditions occur, the ±20V supplies
will protect the load by limiting the current to 0.55 A and the
+6V supply will protect the load by reducing both voltage and
current simultaneously along the foldback locus as shown in
Figure 4. The ±20V and +6V supplies are self restoring; that
is, when the overload is removed or corrected, the output
voltage is automatically restored to the previously set value.

Operation Beyond Rated Output

The supply may be able to provide voltages and currents
greater than its rated maximum outputs if the line voltage is at
or above its nominal value. Operation can be extended up to
5% over the rated output without damage to the supply, but
performance can not be guaranteed to meet specifications in

Summary of Contents for E3630A

Page 1: ... 287387 32 5 6833 3 02 6963 23 5 7 1 0 18 25 167580 176 7 6 5 180 56 5 834785 1 29 RU LQVWUXPHQWV ZLWK 6HULDO 1XPEHUV DERYH 5 834785 D FKDQJH SDJH PD EH LQFOXGHG1 0DQXDO 3DUW 1R1 8 8 0865 ü XJXVW 4 GLWLRQ 9 ...

Page 2: ... personnel Do not replace compo nents with power cable connected Under certain conditions dangerous voltages may exist even with the power cable removed To avoid injuries always disconnect power dis charge circuits and remove external voltage sources before touching components DO NOT SERVICE OR ADJUST ALONE Do not attempt internal service or adjustment unless another person capable of rendering fi...

Page 3: ...lectrical Check 1 6 INSTALLATION DATA 1 6 Location and Cooling 1 6 Outline Diagram 1 6 Rack Mounting 1 6 INPUT POWER REQUIREMENTS 1 6 Power Cable 1 6 OPERATING INSTRUCTIONS 1 6 INTRODUCTION 1 6 TURN ON CHECKOUT PROCEDURE 1 7 OPERATION 1 7 Tracking Ratio Control 1 7 Overload Protection Circuits 1 7 Operation Beyond Rated Output 1 7 Connecting Load 1 8 Parallel Operation 1 8 Series Operation 1 8 LOA...

Page 4: ...erence between your instrument and the instrument described by this manual The Change Sheet may also contain information for correcting errors in the manual OPTIONS Options OE3 and OE9 determine which line voltage is selected at the factory The standard unit is configured for 115 Vac 10 47 63 Hz input Option No Description OE3 230 Vac 10 47 63 Hz Input OE9 100 Vac 10 47 63 Hz Input 910 One additio...

Page 5: ...ROWDJH VHWWLQJ1 8QEDODQFHG ORDGV ZLWKLQ FXUUHQW UDWLQJ DUH SHUPLWWHG1 3 WR 9 9 2XWSXW 0D LPXP UDWHG RXWSXW FXUUHQW LV 518 DW 9 91 7KH PD LPXP DYDLODEOH RXWSXW FXUUHQW GHFUHDVHV ZLWK WKH RXWSXW YROWDJH VHWWLQJ1 FXUUHQW IROGEDFN FLUFXLW OLPLWV WKH RXWSXW WR 51 8 8 DW 9 YROWV DQG ZLWK GHFUHDVLQJ YROWDJH UHGXFHV WKH FXUUHQW OLPLW OLQHDUO WR 4 48 DW HUR YROWV VKRUW FLUFXLWHG 1 75 1 85 7KH 53 9 DQG 053 ...

Page 6: ...Diagram Figure 1 illustrates the outline shape and dimensions of the supply Rack Mounting This supply may be rack mounted in a standard 19 inch rack panel either by itself or alongside a similar unit Please see the ACCESSORY page 1 4 for available rack mounting accessory The rack mounting kit includes complete installa tion instructions INPUT POWER REQUIREMENTS Depending on the line voltage option...

Page 7: ...voltage add the voltmeter readings of the 20V and 20V output and use either the 20V or the 20V meter to measure the current Tracking Ratio Control With the Tracking Ratio control in the Fixed position the volt age of the 20V supply tracks that of the 20V supply within 1 for convenience in varying the symmetrical voltages needed by operational amplifiers and other circuits using bal anced positive ...

Page 8: ...ity diode con nected across the output terminals so that if operated in series with other supplies damage will not occur if the load is short circuited or if one supply is turned on separately from its series partners When this connection is used the output volt age is the sum of the voltages of the individual supplies Each of the individual supplies must be adjusted in order to obtain the total o...

Page 9: ...1 9 Figure 4 Reverse Current Loading Solution ...

Page 10: ......

Page 11: ...URP DQRWKHU FRXQWU 3 VKDOO SD IRU UHWXUQ RI SURGXFWV WR XVWRPHU1 DUUDQW VHUYLFHV RXWVLGH WKH FRXQWU RI LQLWLDO SXUFKDVH DUH LQFOXGHG LQ 3 V SURGXFW SULFH RQO LI XVWRPHU SD V 3 LQWHUQD0 WLRQDO SULFHV GHILQHG DV GHVWLQDWLRQ ORFDO FXUUHQF SULFH RU 8161 RU HQHYD SRUW SULFH 1 I 3 LV XQDEOH ZLWKLQ D UHDVRQDEOH WLPH WR UHSDLU RU UHSODFH DQ SURGXFW WR FRQGLWLRQ DV ZDUUDQWHG WKH XVWRPHU VKDOO EH HQWLWOHG W...

Page 12: ...e Manual of the E3630A Triple Output Lab Bench DC Power supply Manual Part Number 5959 5329 Manual Print Date August 1999 Edition 6 For Instruments with Serial Numbers KR71810198 Change 1 On page 1 5 change the Meter Accuracy Specification at the Table 1 as follows From 0 5 of full scale 2 counts at 25 C 5 C To 0 5 of output 2 counts at 25 C 5 C E3630 90092 E3630 90092 Ó Copyright Hewlett Packard ...

Reviews: