Product Description

Product Description

Product Description

Product Description

HP Modular Cooling System or MCS is designed for high density server and blade deployments. It re-
circulates and cools the hot server exhaust air through heat exchangers residing in the MCS unit. The air
is then expelled in front of the enclosed rack at a much lower temperature providing sufficient cool air for
a load of 35kW of servers or blades.
The MCS unit contains three fans and three heat exchangers deployed along the full height of the rack to
ensure that all the equipment installed receives sufficient cooled air. All fans and heat exchangers are
swappable while the unit is online, providing great servicing flexibility. Redundant power is ensured
through a failover power switch that can be connected to two power sources. The environmental monitor
controls the air temperature to the servers and adjusts automatically to meet the pre-established air
temperature goal. The environmental monitor interacts with HP SIM (Systems Insight Manager) via SNMP
traps.
The Water Hookup kit is made available as a separate kit to prepare the water hookup ahead of the
arrival of the MCS.
A Site Preparation Guide is available for download at 

http://www.hp.com/go/MCS

. This guide provides

details on how to prepare the datacenter for the successful deployment of the MCS. It may be advisable
to contact HP Professional Services for a Site Datacenter Thermal Quick Assessment Service, reference
HB691A1 and HB691AE. Visit 

http://www.hp.com/hps/support

 for additional information.

The MCS unit mounted next to a HP 10000 G2 Series rack is designed to occupy 1.5 tiles in the
datacenter maintaining tile count for cable routing and access to the plenum.

The MCS is now CTO capable with a dynamic load capacity of 2000 Lbs. For HP CTO services go to

http://h20219.www2.hp.com/services/cache/119416-0-0-225-121.html?jumpid=reg_R1002_USEN]

NOTE: 

NOTE: 

NOTE: 

NOTE: A loaded MCS unit should only be moved by professional movers.

HP 10000 G2 Series

HP 10000 G2 Series

HP 10000 G2 Series

HP 10000 G2 Series
Rack

Rack

Rack

Rack

All HP rack-mountable products are designed to fit our industry-standard 19-inch wide racks. Racks and
rack-mountable components are typically described using "U" measurements. One "U" is 1.75" (44.45
mm) high.
The MCS ships attached to a specially adapted 42U 10000 Series G2 rack 600mm wide (10642). This
sturdy, industrial-strength rack series offers the following features:

Universal

Universal

Universal

Universal - Accommodates all HP equipment (ProLiant, Integrity, Integrity NonStop, HP 9000,
Alpha, StorageWorks,) in addition to select third party equipment.
Design

Design

Design

Design - The doors on the HP 10000 G2 Series rack bayed to the MCS unit will be fitted with
Plexiglas mounted inside the front door and solid split rear doors to prevent air from escaping to
the environment.
Load Capacity

Load Capacity

Load Capacity

Load Capacity - The 10642 G2 will accommodate up to 2000 lb. of equipment in a static or
dynamic environment. A static environment is one where the rack is positioned into place and the
leveling feet are extended prior to equipment being installed. A dynamic environment is one where
the rack is shipped on a shock pallet with equipment installed or rolling racks with equipment
installed to new locations within the data center.
Unique Frame and Rail Design

Unique Frame and Rail Design

Unique Frame and Rail Design

Unique Frame and Rail Design - Enables fast assembly, easy mounting and outstanding structural
integrity. Equipment installation effort is dramatically reduced because the vertical mounting
system was specifically designed to minimize the time required to install HP products, and can be
used with many other non-HP products as well. U markings on the front and sides of rails make it
easy to align parts when installing equipment. Cut outs in the rails also allow for cabling between
racks.
Security Provisions

Security Provisions

Security Provisions

Security Provisions - Front and rear doors are lockable, which provides the necessary level of

QuickSpecs

HP Modular Cooling System

HP Modular Cooling System

HP Modular Cooling System

HP Modular Cooling System

Standard Features

DA - 12404   Worldwide — Version 8 — September 17, 2008

Page 4

Summary of Contents for AF058A

Page 1: ...p from 30kW CTO capability of up to 2000 Lbs dynamic load The MCS now ships standard with heavy duty Shock Pallet to support shipping the MCS integrated with IT equipment Customers may now use the services of Factory Express or other integration services QuickSpecs HP Modular Cooling System HP Modular Cooling System HP Modular Cooling System HP Modular Cooling System Overview DA 12404 Worldwide Ve...

Page 2: ...iling configuration Ships pre attached to HP 10642 G2 Series Rack Environmental Monitor and control with SNMP integration to Systems Insight Manager SIM Hot swappable heat exchangers and fans Power Input Redundancy for dual power source Condensate Evacuation system to prevent condensation from entering air stream 2750 CFM of chilled air placed in front of the servers and or blades Site Preparation...

Page 3: ...em MCS HP Modular Cooling System WW CTO ready AF098A HP 10642 G2 Rack Rear Extension Kit NOTE NOTE NOTE NOTE Extension kit is required when racking p Class Blade enclosure combined with Monitored PDU s AF058A MCS Onsite Installation NOTE NOTE NOTE NOTE Install MCS per the product user installation manual All MCS units ship with shock pallet for CTO UE005E NOTE NOTE NOTE NOTE The Rack Rear Extensio...

Page 4: ...E NOTE NOTE NOTE A loaded MCS unit should only be moved by professional movers HP 10000 G2 Series HP 10000 G2 Series HP 10000 G2 Series HP 10000 G2 Series Rack Rack Rack Rack All HP rack mountable products are designed to fit our industry standard 19 inch wide racks Racks and rack mountable components are typically described using U measurements One U is 1 75 44 45 mm high The MCS ships attached t...

Page 5: ...nstalled Disk Drives Tape Drives CD DVD ROM SCSI Hubs in SBBs Adapters Bus Converters Backplane RAID Controllers Power Supplies Cabling Fans Service and Support Service and Support Service and Support Service and Support Offerings Offerings Offerings Offerings HP Care Pack Services HP Modular Cooling System One year warranty parts only 1 0 0 HP 10642 G2 Series Rack Three year warranty parts only 3...

Page 6: ...limited warranty statements accompanying such products and services NOTE NOTE NOTE NOTE Nothing herein should be construed as constituting an additional warranty HP shall not be liable for technical or editorial errors or omissions contained herein QuickSpecs HP Modular Cooling System HP Modular Cooling System HP Modular Cooling System HP Modular Cooling System Standard Features DA 12404 Worldwide...

Page 7: ...ys Kits Rack Top Cable Tray 600W 8 Pack 383982 B21 Rack to Rack Adjustable Cable Tray Aisle Transfer Bridge 383984 B21 Rear Extension Kits Rear Extension Kits Rear Extension Kits Rear Extension Kits 10642 G2 Rear Extension Kit 155mm NOTE NOTE NOTE NOTE The 10642 G2 extension kit is required when using HP monitored PDU s AF058A Service and Support Service and Support Service and Support Service and...

Page 8: ...ent Cooling agent Cooling agent Primary or auxiliary chilled water supply Condensate evacuation Condensate evacuation Condensate evacuation Condensate evacuation tube tube tube tube Yes Air temperature Air temperature Air temperature Air temperature regulation regulation regulation regulation Yes Heat exchangers Heat exchangers Heat exchangers Heat exchangers 3 Fans Fans Fans Fans 3 Rack Front doo...

Page 9: ...ns USA Japan Japan Japan Japan NEMA L6 20P Input Connections Input Connections Input Connections Input Connections International International International International IEC309 16 Amps Power Cords Power Cords Power Cords Power Cords 2 for redundancy Power input redundancy Power input redundancy Power input redundancy Power input redundancy Yes with auto failover switch Environment Environment Env...

Page 10: ...ts returned to HP will be recycled recovered or disposed of in a responsible manner The EU WEEE directive 2002 95 EC requires manufacturers to provide treatment information for each product type for use by treatment facilities This information product disassembly instructions is posted on the Hewlett Packard web site at http www hp com go green These instructions may be used by recyclers and other...