20
3.5
Opening dimension UltraOil
®
(65,80)
(All dimensions in mm)
Boiler without casing and insulation
Fig. 26
Required min. width of door and corridor
to bring in the boiler.
The following values are the calculated minimum values.
150
K
L
B
T
B
K =
x L
T
B
T =
x L
K
Fig. 27
T = Door width
K = Corridor width
B = Boiler width
L = Max. length of boiler
Calculation example for the necessary corridor width
Door width T = 800
680
UltraOil
®
(65,80) K = ----- × 1072 = Corridor width ≥ 912
800
4 213 787 / 01
TECHnICAL DETAILS
Summary of Contents for UltraOil 65
Page 43: ...43 4 213 787 01...