background image

4 200 191 / 01

9

Please note!

In the case of operating faults please
carry out the checks according to the list
above.

If you are unable to rectify the
fault, please call the heating
installer or the Hoval after-sales
service.

Checklist in the case of faults

Fault

Check/Cause

Rectification

See page

Gas boiler

-

Is current present

-

Check fuses, switch on main or where applicable,

does not start

emergency switch

-

Is the gas cock open

-

Open

-

Is a number flashing on the basic control

-

Press reset button

-

Notify after-sales service

-

Is gas present

-

Enquire at your gas supplier

Radiators

-

Are the gate valves in the heating feed

-

Open

are not hot

and return open

-

Is the main switch in the

-

Changeover

6

”OFF” position

-

Is the clock of the TopTronic

-

Carry out check according to the separate operating

correctly set

instructions for the heating controller

-

Check the water level, respectively pressure

-

Refill and bleed the system

4

-

Are the radiator valves open

-

Open

-

The heating circulation pump is not running

-

Remove sealing screw
Turn end of shaft vigorously with a screwdriver
until resistance ceases.

-

The mixer does not open automatically

-

Open manually, call service

No

-

The filling pump is not running

-

Remove sealing screw

hot water

Turn end of shaft vigorously with a screwdriver
until resistance ceases.

-

Is there air in the filling pipeline

-

Bleed manually where applicable

-

Actuate automatic bleeding by hand

-

Has the temperature limiter been activated

-

Unscrew nut and unlock by pressing the knob.

Summary of Contents for UltraGas AM condens (50-350)

Page 1: ...Liquid gas Heating pump type Heating controller type Mixer type Separate calorifier type Calorifier sensor Thermostat Outside temperature sensor Room temperatur sensor Combustion air supply Room Outs...

Page 2: ...operation of your Hoval UltraGasAMcondens allapplicablelaws regulations and standards must be complied with in particular the regulations of the responsible energy supply authorities In the case of qu...

Page 3: ...eating controller If the boiler is also used for water heating it remains switched on for the whole year Fuel The boiler is only to be operated with the type of gas stated on the rating plate Settings...

Page 4: ...e reset button on the boiler control panel If this is not successful please close the gas cock and call your after sales service or heating installer Absolutely imperative Fault freefunctionisonlyguar...

Page 5: ...ed boiler temperature at the boiler temperature controller Please refer to the section Faults on page 4 if fault lamps light Placing out of operation Place the main SYSTEM switch to 0 Close the gas sh...

Page 6: ...ng nor mal Check 6 3A fuse if all displays remain dark Controls the internal boiler functions Settings and changes are only to be made by the heating specialist The indication flashes if a fault is pr...

Page 7: ...ting Automatic control corresponding to the switching times entered for the 3 nd program longer operating time The room temperature is not reduced in the night Hot water according to clock program 2 S...

Page 8: ...to safely break the connection Note the water quality Drinking water quality the pH value must not exceed 9 5 Fill with water slowly check the water level at the hydrometer or pressure gauge Keep the...

Page 9: ...urn open Is the main switch in the Changeover 6 OFF position Is the clock of the TopTronic Carry out check according to the separate operating correctly set instructions for the heating controller Che...

Page 10: ...oors and windows closed in the winter Close flue flaps when the fire is out Use kitchen and bathroom fans only when steam and odours have to be extracted Ventilate for short periods but frequently Sea...

Page 11: ...d set up for optimal operation Any repairs will be carried out at once with your agreement Amaintenancecontractcarriesawiderange of benefits Your guarantee period is extended when you take out a maint...

Page 12: ...p Tel 031 818 66 30 Fax 031 818 66 31 kc bern hoval ch Z rich Postfach 8706 Feldmeilen Tel 0848 81 19 30 Fax 0848 81 19 31 kc zuerich hoval ch Zentralschweiz Postfach 8706 Feldmeilen Tel 0848 81 19 40...

Reviews: