4 213 321 V01 KDT RegelModul Solar EN.docx
8 / 95
3.
Technical data
Designation/type
TopTronic E
Solar module
TopTronic E
Module expansion
Abbreviation
TTE-SOL
TTE-FE
Power supply max
230 V AC +6 - 10%
230 V AC +6 - 10%
Frequency
50 – 60 Hz
50 – 60 Hz
Max. power consumption incl.
bus supply,
module expansions
18.9 W
1.8 W
Max. power consumption
7.8 W
1.8 W
Fuse
10 A slow-blow
None - protection
via controller module
Outputs (high-voltage)
Fully electronic relays
0
0
Electromechanical relays
3
3
Outputs (extra-low voltage)
Signal output PWM or 0-10V
1
1
Switching capacity
Electromechanical relays
2 (2) A
2 (2) A
Inputs (high-voltage)
Optocoupler input
1
1
Inputs (extra-low voltage)
Input 0-10V
1
1
Inputs sensors
2
2
Inputs flow rate sensor
1
1
Pulse input
1 (can be switched over to sensor)
1 (can be switched over to sensor)
Voltage measuring circuit
15 V, with protective isolation 2.9 kV
15 V, with protective isolation
2.9 kV
Expansion (module expansion)
max. number
2
-
Casing
Assembly
Top hat rail mounting (35x15)
Top hat rail mounting (35x15)
Dimensions W/H/D in mm
incl. plug
150x100x75
150x100x75
Ambient temperature
0 … 50 °C
0 … 50 °C
Storage temperature
- 20 ... 60 °C
- 20 ... 60 °C
Bus system (Hoval CAN bus)
Capacity
Max. 4 control modules /
3 control m 1 gateway
-
Bus supply
Yes
None
Bus line
4-wire bus
-
Bus length
Twisted, shielded, max. 100 m
-
Line cross-section
Min 0.5 mm²
-
Other bus interfaces
Internal unit bus (master)
Internal unit bus (slave)
-
-
Miscellaneous
Spring reserve
10 years, battery buffered
-
Type of protection
IP 20
IP 20
Protection class
II – EN 60730
II – EN 60730
Plug types
Rast5 (coloured, coded)
Rast5 (coloured, coded)