background image

 

Mains voltage connection  

 

 

The power supply is 230 V AC; +/-10%.  

 

 

The power cable is connected to the DRHX on the terminals marked ”L”, ”N” and ”PE”. 
See fig. 13.12, or table 11 on page 2. 

 

 

It is recommended that the PE wire is 20 mm longer than the other wires in the cable.  

 

If the cable is accidentally pulled out of the DRHX while there is voltage on the cable 
and terminals, the PE wire will then be the last to be disconnected.  

 

DRHX is thus prevented from causing electric shock. 

 

 

When the stripped wire is properly inserted into the terminal the terminal automatically 
tensions. 

 

 

Remember to 

re-tighten the cable glands

 to ensure the ingress protection level 

of the DRHX and to provide cable strain relief.  

 

Cable  

 

 

Because the stepper motor cable from factory is directly connected into the motor 
windings, 

it is not allowed to be replaced nor shortened

.  

 

 

The motor cable is correctly assembled when the locking pawl on both sides of 
the connector is locked in place with the connector from the cable from the DRHX 
(extension cable).  

 

 

The connector can be separated again by releasing the locking pawl on both 
sides of the connector on the motor cable and pulling the 2 connectors apart. 

 

 

The extension cable should be connected to the terminals marked: 

 

– Brown,  V -  Black, W – Blue,  PE - Yellow/Green  

 
 
 
 
 
 
 
 
 

 

If rotation of rotor is wrong:  
switch the "V" (black) and "W" (blue) cable to change motor direction. 

 

Analogue/digital signal connections 

 

 

Connect A/D control signals to the terminal strip,  
see fig. 13.15. 0-10V = terminal 1 + 2  

 

 

Max. wire dimension is 0.75 mm2 for control terminals. 

 

 

For further information on using the spring terminals, 
see fig. 13.10.1 

 
0-10 V control Which terminals! 

 

 

DRHX is factory-configured for 0-10 V control (this can  
be changed Modbus operation*) 

 

 

The motor starts when there is a control signal over 1.1 V  
(threshold value) 

 

 

The motor stops when control signal is less than 0.6 V 

 

 

The motor runs at maximum speed when there is a control signal over 9.5 V  

 

*RS-485 interface control: DRHX can be controlled via Modbus or BACnet MSTP commands according to 
the Modbus / BACnet MSTP protocols (see separate documentation on OJ Electronic homepage) 

Summary of Contents for DRHX-1055 MAD5

Page 1: ...efore connecting mains voltage to the DRHX controller all components i e stepper motor belt pulley and rotor must be installed correctly all openings covers and cable glands must be properly fitted and closed To maintain the specified enclosure rating unused cable glands should be replaced with blank glands plug Controller DRHX contains capacitors which become charged during operation These capaci...

Page 2: ...m 50Hz 150 170 200 400 rpm Voltage Input 50 60Hz V 1x230 1x230 1x230 Motor voltage V 3x0 200 V AC 3x0 200 V AC 3x0 200 V AC Motor power kW 0 055 0 110 0 220 Rated current A 0 6 2 4 2 4 Class of protection IP54 IP54 IP54 Weight motor kg 2 4 3 5 5 Weight controller kg 0 9 0 9 0 9 Shaft Ø motor mm 12 12 12 8 Nm torque at max 250 motor rpm but only max 5 Nm torque at max 400 motor rpm 6 ...

Page 3: ... to avoid false alarms and errors it is important to install it proper The stepper motor comes with four holes for attachment to a solid mounting plate The mounting plate must be firmly attached to the chassis of the rotary heat exchanger or AHU see figure 12 2 1 marked 1 Do not use vibration dampers or springs Must be mounted on a fixed motor bracket ELECTRICAL INSTALLATION Potential equalization...

Page 4: ...pushing the wire into the terminal without using tools Alternatively the terminal spring can be loosened by pressing it lightly with a screwdriver or similar implement See fig 13 9 Stripped wire ends or end sleeves must be between 8 and 10 mm Wires can be removed by carefully loosening the terminal spring by pressing lightly with a screwdriver or similar implement See fig 13 9 Cable entries cable ...

Page 5: ...the connector from the cable from the DRHX extension cable The connector can be separated again by releasing the locking pawl on both sides of the connector on the motor cable and pulling the 2 connectors apart The extension cable should be connected to the terminals marked U Brown V Black W Blue PE Yellow Green If rotation of rotor is wrong switch the V black and W blue cable to change motor dire...

Page 6: ...changer from Hoval The DRHX series is equipped with 4 DIP switches for setting e g the stepper motor size and maximum motor speed DIP 1 2 motor size DIP 3 4 motor rpm see table 15 1 1 and 15 1 2 Required motor rpm is calculated by Hoval Depends on rotor Ø pulley Ø rotor and motor torque and given rotor rpm See table 15 1 3 Table 15 1 3 ...

Page 7: ... long the button is pressed in Running Test for RHE Belt should be mounted on rotor and pulley Start the test by pressing and continuously holding the test button The controller will enter test mode Visible in display and LED will be orange The test will remain active until the test button is released During this test run the motor will rotate with a maximum speed of 100 rpm Stop the test by relea...

Page 8: ...ies of rotor monitoring systems internal and external The factory setting is Internal rotor guard external is an option Hoval option RG3 Internal rotor guard The internal rotor guard monitors the rotation of the rotor by measuring the electronical signal returning from the motor will take place every 10 seconds After five consecutive failed detections within 1 hour the alarm E01 is given see page ...

Page 9: ...g signal Built in protection If the temperature inside DRHX overstep 95 C DRHX will attempt to reduce its internal heat generation by reducing the amount of current that is sent to the stepper motor DRHX has built in current limitation for the protection of stepper motor and cables and can therefore not supply more current than it is rated to see technical data page 2 DRHX is short circuit protect...

Page 10: ...turn green See point 8 7 If the stepper motor continues to run for more than one minute a recalibration needs to be done Recalibration Press and keep pressing the test button until LED flashes orange can take 10 50 sec Remove your finger from the button and the LED will turn green the pulley internal rotor guard has been calibrated 8 After turn off the DRHX controller and mount the belt Start norm...

Page 11: ...st page 10 Make the test calibration again see page 10 If the motor is too powerful for the rotors load large motor to a very small load The rotor torque is lower than the internal rotor guards minimal torque limit for chosen type of DRHX MRHX system i e spare part for old RHE Exchange type of MRHX motor and if needed DRHX controller so its fits the rotor type Contact Hoval for support E06 Wobblin...

Page 12: ...at the DRHX has a signal connected to the Start Stop input digital input Din 1 2 or 3 depending on the configuration Lacking 0 10 V DC control signal Check that DRHX receives an operating signal 1 1 V on 0 10 V In Active alarm Read active alarms via the display and remove what is causing the alarm see page 11 can also be read by using DRHX PC Tool or via Modbus The stepper motor has been stopped 5...

Reviews: