4 209 973 / 00

Fault Indicator Type WP-VT (2141)

 

Alarm 

 

Display   flashing 

Meaning 

Effect/action

  

  1 

• No 1 

 

red 

red 

Temperature sensor in 

Heat pump and additional 

 

   

 

 

 

the upper tank -  

heating is shut down.

• No 2 

 

red 

red 

faulty or defective 

Inform service.

• No 3 

 

red 

Temperature sensor in 

Compressor not running. 

  

  

   

 

evaporator

  

   

 

 

Inform service.

• No 4 

 

red 

Faulty or defective 

Replace defective sensor.

• No 5 

 

red 

1. Pressure switch alarm 

compressor shuts down and   

   

 

 

 

(High-pressure fault) 

restarts automatically. Eliminate 

   

 

 

 

 

fault / inform service. maybe    

   

 

 

 

 

Acknowledge (see page 5)

• No 6 

   red 

2. Pressure switch alarm 

and acknowledge in user menu  

  

   

 

(high-pressure fault)

 

It is essential to inform service

 

 

 

 

  

 

 

    

 
• No 7 

 

red 

 

For information: not relevant

  

   

 

 

(inactive)

• No 8 

 

red 

Temperature sensor 

Information:

   

 

 

 

„Temp 1“ 

Inform service. Replace

   

 

 

 

faulty or defective 

defective sensor.      

 

  

   

 

 

(Service-Program)   

 
• No 9 

 

red 

Protective magnesium  

Information: 

 

 

   

 

 

 

anode exhausted 

Install new protective anode.

   

 

 

 

 

Inform service.

• No 10 

 

red 

Legionella temperature 

Information : 

 

 

   

 

 

 

not reached 

Check settings.

   

 

 

 

 

Inform service.

Alarm overview / fault overview

Alarm/fault overview WP-VT

Alarms and faults can be seen in the user level (alarm mode) and acknowledged.  

 

If the error is not eliminated, then, even if acknowledged, the alarm display remains. If several alarms/faults arise,   
they are placed in sequence and shown as a priority list. The alarms/faults are divided into 3 groups (alarm levels).

Alarm group 

Alarm-No 

Status/Effect 

Remarks/Action

1  General equipment alarm 

1 and 2  

Equipment is turned off/  No hot water/ see table  

 

 

 

 

 

no operation possible 

below 

 

 

 

 
2  Working fluid circulation 

3, 4, 5 

Heat pump is shut down/ Hot water with additional heating, 

 

Alarm (heat pump) 

and 6 

operation only possible   switch on additional heating/ see 

 

 

 

with additional heating.  table below

3  Information 

6, 7, 8 

Operation remains  

irregularities in operation/

 

 

9 and 10 

possible/ the displayed    see table below

 

 

 

alarms must be 

 

 

 

eliminated soon  

 

1  Heat pump operation and fault  
  display. Flashing red = fault in   
  alarm group 2 or 3
2. Additional heating operation and  
  fault display (boiler or immersion  
 heater)

If both displays (1+2) are flashing 
red = fault in alarm group 1

 

3  Display   

 

Alarm

  9    0    0

Acknowledge = 
press knob

Control Panel

1 2 3

Fault Indicator

Summary of Contents for CombiVal WP-VT

Page 1: ...to modifications Operating Instructions Hoval United Kingdom Hoval LTD Northgate Newark Nottinghamshire NG24 1JN Phone 44 1636 67 27 11 Fax 44 1636 67 35 32 Hoval Export Hovalwerk AG Austrasse 70 9490 Vaduz Principality of Liechtenstein Phone 423 399 24 00 Fax 423 399 26 18 ...

Page 2: ...__________________________________ ______________________________________ Tel No ________________________________ Electrician ______________________________________ ______________________________________ ______________________________________ Tel No ________________________________ Important addresses Important addresses 2 Safety Instructions 3 Product Description and Mode of Operation 4 Fault Ind...

Page 3: ...it has been ap proved by Hoval Do not make any modifications to the equipment as this will result in invalidating all legal claims Con version kits must be installed by and obtained from the licensed installer or Hoval Customer Ser vices In the event of damage or mal function find out about the repairs required from Hoval Customer Services To prevent any damage it is essential that the equipment b...

Page 4: ... use with normal drinking water No guarantees can be given if drinking water of above average aggressivity is used The protective anode should be checked regularly and if necessary exchanged by your installer or by Hoval Customer Service This is a condition of the guarantee fig 1 The magnesium protective anode must under all circumstances be renewed if the diameter is down to only 10 mm Fig 1 Prot...

Page 5: ... Acknowledge Press 3 Alarm fault Heat pump in hot water mode Further data Off Standby Legionella heating up to 65 C in operation De icing mode De icing gas De icing air De icing off De icing stop 4 Operating status data 5 Target temperature of hot water Set point Target hot water temperature Flashing Setpoint 45 C 3 Press knob acknowledge the new set temperature is now effective The setting should...

Page 6: ... the pump and or electrical heating and or the boiler The function of the water heating operation is controlled by the user program heat pump operational status W Wasser Temperature control by sensors Tmax set point and Tmin The heat pump is switched on if the temperature falls below the set value is reached If the heat pump is switched off the target temperature of the heat ing water is reached w...

Page 7: ...ttings Inform service Alarm overview fault overview Alarm fault overview WP VT Alarms and faults can be seen in the user level alarm mode and acknowledged If the error is not eliminated then even if acknowledged the alarm display remains If several alarms faults arise they are placed in sequence and shown as a priority list The alarms faults are divided into 3 groups alarm levels Alarm group Alarm...

Page 8: ... not in standby position High pressure fault Condensate drainage blocked No drainage siphon installed No water in drainage siphon Fault Alarm signal in display Electrical fault no display Electrical heating does not heat up although switched on Additional heating does not heat up although it is switched on Fault No 5 or 6 Condensate leak during operation Smell You can minimise the risk of a fault ...

Page 9: ...e tight From time to time check to ensure that the operating voltage and phase ir regularity remains within the specified limits Performance monitoring The temperature difference between the inlet air and exhaust air should be approximately 5 7K Greater tempera ture differences point towards prob lems in air throughput check both inlet and exhaust air flow whereas differ ences smaller than 4K indi...

Page 10: ...y Hoval Deutschland GmbH Karl Hammerschmidt Strasse 45 D 85609 Aschheim Dornach Phone 49 89 92 20 97 0 Fax 49 89 92 20 97 77 www hoval de Austria Hoval Gesellschaft mbH Hovalstrasse 11 A 4614 Marchtrenk Phone 43 50 365 0 Fax 43 50 365 5005 www hoval at Italy Hoval Italia S r l Via per Azzano San Paolo 26 28 I 24050 Grassobbio BG Phone 39 035 52 50 69 Fax 39 035 52 58 58 www hoval it France Hoval F...

Reviews: