34
Output Rated Voltage: Select the output rated voltage. There are three options, 220Vac,
230Vac and 240Vac. 220Vac is default setting.
Output Rated FREQ: Select the output frequency
50Hz: The output frequency is setting for 50Hz.
60Hz: The output frequency is setting for 60Hz.
50Hz is default setting.
CVCF Mode (constant voltage and constant frequency function)
Enable: CVCF function is enabled. The output frequency will be fixed at 50Hz
or 60Hz according to setting of “OP Freq.”. The input frequency could be from
40Hz to 70Hz.
Disable: CVCF function is disabled. The output frequency will synchronize with
the bypass frequency within 45~55 Hz for 50Hz system or within 55~65 Hz for
60Hz system. Disable is the default setting.
Line Voltage Range: Set the acceptable line input voltage range.
L
: Low voltage point for line voltage. The setting range is 165V ~ 225V. 165V is
default setting.
H:
High voltage point for line voltage. The setting range is 235V ~ 280V. 280V is
default setting
Line FREQ Range: Set the acceptable line input frequency range.
L
: Low frequency point for line voltage. The setting range is 45Hz ~ 49Hz for
50Hz system and 55Hz ~ 59Hz for 60Hz system. 46Hz is default setting for
50Hz system and 56Hz is default setting for 60Hz system.
H
: High frequency point for line voltage. The setting range is 51Hz ~ 56Hz for
50Hz system and 61Hz ~ 66Hz for 60Hz system. 54Hz is default setting for
50Hz system and 64Hz is default setting for 60Hz system.
Bypass Forbid:
Disable
: Bypass allowed. When selected, UPS will run in Bypass mode
depending on “Byp.at off” setting. It is the default setting.
Enable
: Bypass not allowed. When selected, it’s not allowed for running in
Bypass mode under any situations.
Bypass at UPS off: Select the bypass status when manually turning off the UPS. This
setting is only available when “Bypass forbid.” is set to “Disable”.
Enable
: Bypass enabled. When selected, bypass mode is activated.
Disable
: Bypass disabled. When selected, no output through bypass when
manually turning off the UPS.
Summary of Contents for Orion Series
Page 16: ...14 The wire terminals of each model are shown as below 10K 30K 40K 60K 80K 120K 160K 200K ...
Page 28: ...26 Turn On Off UPS Turn On UPS Turn Off UPS Battery Test Do Battery Test ...
Page 29: ...27 Cancel Battery Test Audio Mute Active Audio Mute Cancel Mute ...
Page 46: ...44 Initial Initial Setting Menu Page Data Log Initial Page Parameters Initial Page ...