14
Components Energized when the Control Switch is in the SERVICE Position
When in the "SERVICE" position, the control switch supplies power
to the service switch and the machine is
in service mode.
The service switch has three positions: "DRAIN," "CIRC." and "W
ASH." See the information
below for details of each function.
DRAIN
Power is supplied to the pump and drain valve. This drains the wat
er tank.
CIRC.
Power is supplied to the pump only. This operation can be used to
circulate cleaner and
sanitizer for extended periods of time over the outside surface of
the evaporator.
WASH
Power is supplied to the pump and wash valve. This operation is
used to circulate cleaner
and sanitizer over both the inside and outside surfaces of the eva
porator.
4. Pump-Out Cycle
Legend:
Comp
- compressor
DWV -
drain water valve
FMR
- remote fan motor
FWV
- fill water valve
HGV
- hot gas valve
HWV
- harvest water valve
LF/S
- lower float switch contacts
LLV
- liquid line valve
PM
- pump motor
UF/S
- upper float switch contacts
KMS-1400MLH Sequence Flow Chart and Component Operation
1. One Minute
Fill Cycle
2. Harvest Cycle
3. Freeze Cycle
Pump motor stops
for
sec. and then
runs
for 10 sec.
Cycle Steps
FWV
energized
LF/S
open
LF/S
closed
Comp
energized
FMR
energized
HGV
energized
HWV
energized
FWV
de-energized
DWV
de-energized
Thermistor temp
reaches 48
°F (9°C)
(3.9 k
Ω
or less)
Harvest timer starts
LF/S
open
Comp
continues
FMR
continues
PM
continues
LLV
energizes
FWV
energized/
de-energized
for refill only
HGV
de-energized
LF/S
closed
Freeze cycle
operation turned
over to
LF/S
PM
de-energizes
sec. ,
energizes for 10 sec.
Comp
continues
FMR
continues
DWV
energized
HGV
energized
LLV
de-energized
LF/S
check
LF/S
check
• Maximum harvest water valve time: 6 minutes
(HWV time is 6 minutes or the length of
harvest minus 50 sec., whichever is shorter.
PM energizes and runs for the last 50 sec. of
harvest.)
• Maximum harvest time:
0 minutes
Thermistor in
control
1 to 3 minute timer
in control
• Minimum freeze time: 5 minutes
• Maximum freeze time: freeze timer setting
• Lower float switch used to initiate water
tank refill (1 refill for KMS
-1400MLH)
• Upper float switch used to terminate
water tank refill (1 minute maximum fill
time)
5 minute timer
in control
Lower float
switch in
control
Initial startup always
begins here
"G" board will have
5
second delay
If
LF/S
is open, compressor stops and cycle returns to 1 minute fill
Factory set for every
10th cycle
50 sec.
PM
energized
HWV
de-energized