41
5. Bin Control Selector (S1 dip switch 7)
The appliance is factory set for infrared sensor bin control operation. No adjustment is
required. When used on a standard ice storage bin, the mechanical bin control may be
used instead of the infrared sensor by moving S1 dip switch 7 to the off position. In the
factory default position (S1 dip switch 7 in the on position), the gear motor delay after
the upper float switch closes is 30 sec. When the mechanical bin control is used (S1 dip
switch 7 in the off position), the gear motor delay after the upper float switch closes is
5 sec.
WARNING! Do not place S1 dip switch 7 in the off position on dispenser unit
applications. This could lead to icemaker movement or ice overflow.
S1 Dip Switch
Setting
Bin Control Application
Gear Motor Delay
No. 7
OFF
BC (mechanical stand-alone) (Standard Ice Storage Bins Only) 5 seconds
ON
BC1 (infrared sensor) with
BC2 (mechanical backup)
30 seconds
6. BC (Mechanical Stand-Alone) Shutdown Delay (S1 dip switch 8)
Not available when S1 dip switch 7 is on. Factory set for normal operation. No adjustment
is required. The shutdown delay is the time between the mechanical bin control proximity
switch opening and the control board shutting off the icemaker. Note: When used in
conjunction with BC1, shutdown is immediate and CB sounds a 9 beep alarm.
S1 Dip Switch Setting
Mechanical Bin Control
Shutdown Delay
No. 8
OFF
0.25 Seconds
ON
6.7 Seconds
7. Factory Use (S1 Dip Switch 9 & 10)
Factory set for optimum performance. Do not adjust.